16-6
Chapter 16
ProDriveNext / EzSQ
Related parameters (settings)
*1)
If you select a value other than the aforementioned
value for parameters [AA101] (Main speed command)
or [AA111] (Operation command), you can enter speed
or operation command using the operator keypad or
analog signal.
*2)
Assign 099 [PRG] to the input terminal only if you select
01 (Activated by PRG terminal) for [UE-02] (EzSQ
function selection).
EzSQ program activation timing
(1) When [UE-02] (Activated by [PRG] terminal) is set
to 01,
• Assign 099 [PRG] terminal to any of the input
terminals 1 to 9, A and B. The EzSQ program will be
activated when the PRG terminal is turned ON.
• As for variables that require adjustment on the actual
inverter, you can change the data on the operator keypad
without connecting the inverter to a PC if you have
designated the variables to user parameters ([UE-10] to
[UE-73] and/or [UF-02] to [UF-32]).
(2) When [UE-02] (Always active) is set to 02,
• The EzSQ program is constantly active while the
inverter power is ON.
Item
Parameter
Data
Description
EzSQ execution interval
[UE-01]
00
1ms/Step
01
2ms/Step
EzSQ function selection
[UE-02]
00
EzSQ function disabled
01
EzSQ function enabled (Activated by PRG terminal)
02
EzSQ function enabled (Always active)
EzSQ user parameters
U (00) to U (63)
[UE-10]~[UE-73]
0~65535
U (00) to U (63) on the program is operable via the
operator keypad.
EzSQ user parameters
UL (00) to UL (15)
[UF-02]~[UF-32]
-2147483647
~2147483647
UL (00) to UL (15) on the program is operable via
the operator keypad.
Main speed command selection
Auxiliary speed command
selection
[AA101]
[AA102]
14
To set frequency in the SET-Freq variable, select 14
(program function) for these parameters. *1)
Operation command selection
[AA111]
00
To operate and stop the inverter using the variables
FW and RV respectively, select 00 (terminal
[FW]/[RV]) for this operation command parameter.
*1)
Acceleration or deceleration time
input selection
[AC-01]
04
To set acceleration and deceleration time in the
ACCEL and DECEL variables respectively, select
14 (program function) for this parameter.
Input terminal 1 to 9, A or B
selection
[CA-01]~[CA-11]
099
PRG: EzSQ function PRG terminal *2)
Input terminal 1 to 9, A or B
selection
[CA-01]~[CA-11]
086~096
MI1 to MI11: General purpose input 1 to 9, A or B
Output terminal 11 to 15 selection
Relay output terminal selection
16 or AL
[CC-01]~[CC-07]
069~075
MO1 to MO7: General purpose output 1 to 7
Analogue input [Ai1] terminal
- (setting not
required)
-
XA (0): General purpose analog input (0 to 10 V /0
to 20 mA)
Analogue input [Ai2] terminal
- (setting not
required)
-
XA (1): General purpose analog input (0 to 10 V /0
to 20 mA)
Analogue input [Ai3] terminal
- (setting not
required)
-
XA (2): General purpose analog input (-10 to 10 V)
FM output [FM] terminal selection
[Cd-03]
[db-18]
[db-19]
[db-20]
YA (0): General purpose analog output
YA (1): General purpose analog output
YA (2): General purpose analog output
Analogue output [Ao1] terminal
selection
[Cd-04]
Analogue output [Ao2] terminal
selection
[Cd-05]
!
!
Inverter power supply
EzSQ operation
[PRG] terminal input
Normal operation
EzSQ operation
Inverter power supply
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...