18-34
Chapter 18
Tips/FAQ/Troubleshooting
Icon 2 ALT monitor
• The ALT icon is shown on the display.
Icon 2 RETRY monitor
• The RETRY icon is shown on the display.
• When ALT is shown, the inverter is in the following
condition(s).
• You can see the status of ALT by pressing UP key
on the three-lined monitor or on [dC-38].
• When RETRY is shown, the inverter is in the
following condition(s).
• You can see the status of RETRY by pressing UP
key on the three-lined monitor or on [dC-39].
Q
Q
A
A
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Output current was
high, and [dC-38]
ALT was set to 01.
• The current increased due to load or other factors,
exceeding the overload prewarning levels set in
[CE106] or the similar parameter.
• Remove the factor for the increased load.
(E.g., by cleaning a clogged channel)
• Enable [bA122] overload limit function or
similar function.
Output current was
high, and [dC-38]
ALT was set to 03.
• The electronic thermal function of inverter was
activated due to increase in current and the load
exceeded the electronic thermal warning level
(CTL) set in [CE-31].
• Remove the factor for the increased load.
(E.g., by cleaning a clogged channel)
Output was turned
OFF and [dC-39]
RETRY was set to
01.
• The inverter is in the waiting mode after a trip retry
operation due to increased current or P-N voltage
fluctuation.
• If the wait time become longer, the
following delay time become shorter.
[bb-26] [bb-29] [bb-31]
• If this error is generated consecutively,
make the wait time longer. [bb-26] [bb-29]
[bb-31]
Output was turned
OFF and [dC-39]
RETRY was set to
02.
• The inverter is in the waiting mode before restart
after power-off by [RS], [FRS], or [CS] terminal.
• If the wait time become longer, the
following delay time become shorter.
[bb-26]
Output current was
high, and [dC-38]
ALT was set to 02.
• The electronic thermal function of motor was
activated due to increase in current and the load
exceeded the electronic thermal warning level
(MTR) set in [CE-30].
• Remove the factor for the increased load.
(E.g., by cleaning a clogged channel)
• Re-examine the electric thermal settings in
[bC110] or the similar parameter.
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...