18-35
Chapter 18
Tips/FAQ/Troubleshooting
Icon 2 NRDY monitor
• The NRDY icon is shown on the display.
• When NRDY is shown, the inverter is in the
following condition(s).
• You can see the status of NRDY by pressing UP
key on the three-lined monitor or on [dC-40].
Q
A
Occurrence
Estimated cause(s)
Exemplar measures to be taken
TRIP display was
shown and [dC-40]
NRDY was set to
01.
• There was an error factor, which caused the
inverter to trip.
• Remove the error factor.
Consult this chapter.
The CTRL icon was
shown and [dC-40]
NRDY was set to
02.
• The control power supply (R0, T0) has been
input, whereas the main circuit power supply
R-S-
T hasn’t been input.
• Check the input of main circuit power
supply and examine the breaker, wiring,
and so on.
The 24V icon was
shown and [dC-40]
NRDY was set to
02.
• Only 24V has been input to the backup power
supply P+-P-.
• Check the input of main circuit power
supply and the control power supply, and
examine the breaker, wiring, and so on.
[dC-40] NRDY was
set to 03.
• [RS] terminal is ON and the inverter is under reset
operation.
• Check the wiring and operation state of
[RS] terminal.
[dC-40] NRDY was
set to 04.
• The STO circuit is turned OFF or broken.
• Check ST1/ST2 terminals.
[dC-40] NRDY was
set to 05.
• The inverter is checking the internal circuit,
operator keypad, options, etc.
• If this error is not released, check the
operator keypad for contact failure or other
problem.
[dC-40] NRDY was
set to 06.
• There is an inconsistency in the setting
• Although [AA121] is set to 10 (Vector
control with sensor), the option P1-FB is
not attached.
• Refer to 18.5.2 “Checking setting
inconsistencies”.
[dC-40] NRDY was
set to 07.
• There is a sequence operation problem in the
brake control.
• Check the setting and signal operation of
[AF130] brake control or the similar
parameter.
[dC-40] NRDY was
set to 08.
• [FRS] terminal or [CS] terminal was turned ON.
• [FRS] or [CS] command was entered from the
communication.
• Check the signal operation of input
terminal for [FRS] or [CS].
[dC-40] NRDY was
set to 09.
• Operation command isn’t permitted.
• The [REN] terminal has been assigned
and is turned OFF.
• Forced stop is being issued. (Deceleration stop
behavior)
• STOP key was pressed when commands
had been entered from a source other
than the operation keypad.
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...