12-10-24
Chapter 12
Inverter Functions
Parameter
*3) Data range varies according to [AJ-44] - [AJ-46]
settings.
Input terminal function
Item
Parameter
Data
Description
PID4 selection
[AJ-41]
00
Disable
01
Enable (if command becomes negative, it does not
output in a reverse direction)
02
Enable (if command becomes negative, it outputs in
a reverse direction)
PID4 deviation negative
[AJ-42]
00
Disable
01
Enable (polarity inversion of deviation)
PID4 target value input
destination
[AJ-47]
00~15
00: Disable, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: Ai4-L input, 05: Ai5-L input,
06: Ai6-L input, 07: Parameter setting [AH-44],
08: RS 485 communication,09: P option 1, 10: Option
2
11: Option 3, 12: Pulse train input (main unit),
13:Pulse train input (P1-FB)
PID4 target value set
value
[AJ-48]
0.00~100.00(%)
*3)
Is a parameter set value.
PID4 feedback data
input destination
[AJ-50]
00~13
00: Disable, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: Ai4-L input, 05: Ai5-L input,
06: Ai6-L input, 07: Parameter setting [AH-44],
08: RS 485 communication,09: P option 1, 10: Option
2
11: Option 3, 12: Pulse train input (main unit),
13:Pulse train input (P1-FB)
PID4 proportional (P)
gain
[AJ-53]
0.0~100.0
Proportional gain
PID4 integral (I) gain
[AJ-54]
0.0~3600.0(s)
Integral gain
PID4 differential (D)
gain
[AJ-55]
0.00~100.00(s)
Differential gain
Item
Terminal
name
Data
Description
PID2 disable function
[PID2]
043
Disables the PID2 function by turning ON the terminal
function.
Frequency equivalent to the target value of PID2 will be
commanded when the terminal is turned ON.
PID2 I control integral value
clear
[PIDC2]
044
Clears the integral value of PID2 control.
PID3 disable function
[PID3]
045
Disables the PID3 function by turning ON the terminal
function.
Frequency equivalent to the target value of PID3 will be
commanded when the terminal is turned ON.
PID3 I control integral value
clear
[PIDC3]
046
Clears the integral value of PID3 control.
PID4 disable function
[PID4]
047
Disables the PID4 function by turning ON the terminal
function.
Frequency equivalent to the target value of PID4 will be
commanded when the terminal is turned ON.
PID4 I control integral value
clear
[PIDC4]
048
Clears the integral value of PID4 control.
PID output switch 1
[PIO1]
056
Switches PID output by a combination of PIO1 and PIO2.
PID output switch 2
[PIO2]
057
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...