12-17-13
Chapter 12
Inverter Functions
12.17.6
Performing the Forced Operation
• How to switch to the forced operation mode with
the signal input.
• How to fix an operation mode until the power-off.
• How to enter the operation mode using a
commercial power supply when the inverter cannot
be restarted due to a failure.
• Performing this function enables the inverter to run
in the forced operation mode (Em-Force mode) in
which it operates at a constant speed without
shutting off the inverter output until the power-off.
• Set the [PA-01] forced operation to enabled 01 and
turn on the [EMF] emergency forced operation
terminal (input terminal: 105) to enter the forced
operation mode.
• The command for the forced operation mode is set
with the [PA-02] Em-Force mode frequency setting
and the rotation direction command in the [PA-03]
Em-Force mode.
Parameter Setting
Input Terminal Setting
Output Terminal Setting
• Once the forced operation mode is turned on, the
inverter keeps operating until the power is off.
• When using the forced operation mode, make sure
that the system is safe if the operation continues.
• Enabling the overcurrent retry, overvoltage retry,
undervoltage retry or instantaneous power failure
retry requires a separate setting.
• After the [EMF] emergency forced operation
terminal (input terminal: 105) is turned on, the input
terminal function except for the following are
disabled.
⇒
[COK]: Contactor check signal
Item
Parameter
Data
Description
Em-Force mode
selection
[PA-01]
00
Disabled
01
Enabled
Em-Force mode
frequency setting
[PA-02]
0.00~590.00(Hz)
Set the frequency command in the forced operation
mode.
Rotation direction in
the Em-Force mode
[PA-03]
00
Forward rotation command
01
Reverse rotation command
Item
Parameter
Data
Description
Selecting the input
terminal
[CA-01]~
[CA-11]
105
[EMF] emergency forced operation terminal.
OFF: Disabled
ON: Forced operation mode (when [PA-01] = 01)
Item
Parameter
Data
Description
Selecting the output
terminal
[CC-01]~
[CC-07]
076
[EMFC] Signal in Em-Force.
OFF: Disabled
ON: In the forced operation mode
Q
A
!
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...