12-2-1
Chapter 12
Inverter Functions
12.2 Basic setting of inverter
12.2.1
Change duty rating of inverter
• Want to change the duty rating mode to the one
checked in selecting the mode.
• Want to lower the capacity of the inverter against
the motor since the duty of the fan or pump is
small.
• Want to use the inverter for a lift or others with a
heavy duty.
• The duty rating mode of the inverter can be chosen
from Normal Duty (ND), Low Duty (LD), and Very
Low Duty (VLD). See “Difference in duty rating
modes” in the following.
• The rated current, excess duty endurance, and
rated temperature of the inverter could change
depending on the duty rating mode.
• A change of the inverter duty rating mode is
reflected immediately after the duty type [Ub-03] is
changed.
Parameters
Difference in duty rating modes
*) Feedback option of the optional cassette is
necessary for the vector control with sensor.
• When [Ub-03] is changed, the parameter set for
the electric current is automatically adjusted at the
ratio of the changed rated current and the set
value is changed accordingly.
• Another check is necessary if the electric current is
set by using the excess duty limit function, direct
current control function, electronic thermal function,
excess duty warning function, or low current
detection function.
• When VLD is selected and the control mode is
selected out of the VLD specification range with
the control type [AA121], the control mode is
automatically set to the V/f control. Another check
is necessary when the control type setting is
changed.
Item
Parameters
Data
Description
Duty Type
[Ub-03]
00
VLD (Very Low Duty)
01
LD (Low Duty)
02
ND (Normal Duty)
Duty rating
ND (Normal Duty)
LD (Low Duty)
VLD (Very Low Duty)
Excess duty
endurance
150% (1 min.) 200% (3 sec.)
120% (1 min.) 150% (3 sec.)
110% (1 min.) 120% (3 sec.)
Temperature
characteristics
50 °C (with derating)
45°C (with derating)
40°C (with derating)
Correspondin
g control type
*)
Induction motor IM
• V/f control
• V/f control with sensor
• SLV (sensorless vector)
control
• 0 Hz-range SLV control
• Vector control with sensor
Synchronous motor SM
• SLV control
Induction motor IM
• V/f control
• V/f control with sensor
• SLV (sensorless vector)
control
Synchronous motor SM
• SLV control
Induction motor IM
• V/f control
• V/f control with sensor
• SLV (sensorless vector)
control
Synchronous motor SM
• SLV control
Major
applications
Lifts, cranes, etc.
Conveyors, transportation machines, etc.
Fans, pumps
Q
A
!
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...