14-38
Chapter 14
RS485 Communication
Function
Code
Register
No.
(decimal)
Register
No.
(hexadecimal)
Function Name
R/W
Monitor Content and
Setting Item
Data
Resolution /
Unit
Retry
monitor
(dE-35)
1281
0501h
Retry monitor 5 Factor
R
1 ~ 255
1
1282
0502h
Retry monitor 5 Output
frequency
(High)
R
-59000 ~ 59000
0.01Hz
1283
0503h
(with sign)
(Low)
1284
0504h
Retry monitor 5 Output current
R
0 ~ 65535
0.01A
1285
0505h
Retry monitor 5 P-N DC voltage
R
0 ~ 10000
0.1Vdc
1286
0506h
Retry monitor 5 Inverter state
R
0 ~ 8
1
1287
0507h
Retry monitor 5 LAD state
R
0 ~ 5
1
1288
0508h
Retry monitor 5 INV control mode
R
0 ~ 11
1
1289
0509h
Retry monitor 5 Limit state
R
0 ~ 6
1
1290
050Ah
Retry monitor 5 Special state
R
0 ~ 6
1
1292
050Ch
Retry monitor 5 RUN time
(High)
R
0 ~ 1000000
1hr
1293
050Dh
(Low)
1294
050Eh
Retry monitor 5 Power ON time
(High)
R
0 ~ 1000000
1hr
1295
050Fh
(Low)
1296
0510h
Retry monitor 5 Absolute time (year,
month)
R
00 - 99 (BCD code)
1
01 - 12 (BCD code)
1
1297
0511h
Retry monitor 5 Absolute time (day, day of
the week)
R
01 - 31 (BCD code)
1
00 - 06 (BCD code)
1
1298
0512h
Retry monitor 5 Absolute time (hour,
minute)
R
00 - 23 (BCD code)
1
00 - 59 (BCD code)
1
Retry
monitor
(dE-36)
1301
0515h
Retry monitor 6 Factor
R
1 ~ 255
1
1302
0516h
Retry monitor 6 Output
frequency
(High)
R
-59000 ~ 59000
0.01Hz
1303
0517h
(with sign)
(Low)
1304
0518h
Retry monitor 6 Output current
R
0 ~ 65535
0.01A
1305
0519h
Retry monitor 6 P-N DC voltage
R
0 ~ 10000
0.1Vdc
1306
051Ah
Retry monitor 6 Inverter state
R
0 ~ 8
1
1307
051Bh
Retry monitor 6 LAD state
R
0 ~ 5
1
1308
051Ch
Retry monitor 6 INV control mode
R
0 ~ 11
1
1309
051Dh
Retry monitor 6 Limit state
R
0 ~ 6
1
1310
051Eh
Retry monitor 6 Special state
R
0 ~ 6
1
1312
0520h
Retry monitor 6 RUN time
(High)
R
0 ~ 1000000
1hr
1313
0521h
(Low)
1314
0522h
Retry monitor 6 Power ON time
(High)
R
0 ~ 1000000
1hr
1315
0523h
(Low)
1316
0524h
Retry monitor 6 Absolute time (year,
month)
R
00 - 99 (BCD code)
1
01 - 12 (BCD code)
1
1317
0525h
Retry monitor 6 Absolute time (day, day of
the week)
R
01 - 31 (BCD code)
1
00 - 06 (BCD code)
1
1318
0526h
Retry monitor 6 Absolute time (hour,
minute)
R
00 - 23 (BCD code)
1
00 - 59 (BCD code)
1
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...