14-55
Chapter 14
RS485 Communication
Function
Code
Register
No.
(decimal)
Register
No.
(hexadecimal)
Function Name
R/W
Monitor Content and
Setting Item
Data
Resolution /
Unit
bb101
13101
332Dh
First carrier frequency
R/W
5 to 160 (varies depending
on selection of capacity and
load rating)
0.1kHz
bb102
13102
332Eh
First sprinkle carrier pattern selection
R/W 0 ~ 3
1
bb103
13103
332Fh
First automatic carrier frequency
reduction selection
R/W 0 ~ 2
1
bb-10
13110
3336h
Auto-reset selection
R/W 0 ~ 2
1
bb-11
13111
3337h
Alarm output selection when the
auto-reset is enabled
R/W 0 ~ 1
1
bb-12
13112
3338h
Automatic resetting stand-by time
R/W 0 ~ 600
1s
bb-13
13113
3339h
Automatic resetting count setting
R/W 0 ~ 10
1
bb-20
13120
3340h
Instantaneous power failure retry count
selection
R/W 0 ~ 16 / 255
1
bb-21
13121
3341h
Undervoltage retry count selection
R/W 0 ~ 16 / 255
1
bb-22
13122
3342h
Overcurrent retry count selection
R/W 0 ~ 5
1
bb-23
13123
3343h
Overvoltage retry count selection
R/W 0 ~ 5
1
bb-24
13124
3344h
Selection of instantaneous power
failure/undervoltage retry
R/W 0 ~ 4
1
bb-25
13125
3345h
Allowable instantaneous power failure
time
R/W 3 ~ 250
0.1s
bb-26
13126
3346h
Retry wait time after instantaneous power
failure/undervoltage
R/W 3 ~ 1000
0.1s
bb-27
13127
3347h
Instantaneous power failure/undervoltage
tripping selection during stop
R/W 0 ~ 2
1
bb-28
13128
3348h
Overcurrent trip/retry selection
R/W 0 ~ 4
1
bb-29
13129
3349h
Retry wait time after overcurrent
R/W 3 ~ 1000
0.1s
bb-30
13130
334Ah
Overvoltage trip/retry selection
R/W 0 ~ 4
1
bb-31
13131
334Bh
Retry wait time after overvoltage
R/W 3 ~ 1000
0.1s
bb-40
13140
3354h
Restart after free-run release
R/W 0 ~ 3
1
bb-41
13141
3355h
Restart after reset release
R/W 0 ~ 3
1
bb-42
13142
3356h
Speed frequency matching lower limit
frequency setting
R/W 0 ~ 59000
0.01Hz
bb-43
13143
3357h
Restarting level of frequency acquisition
R/W
(0.20 to 2.00) * CTL rated
current
0.1A
bb-44
13144
3358h
Constant (speed) for frequency
acquisition restarting
R/W 10 ~ 3000
0.01s
bb-45
13145
3359h
Constant (voltage) for frequency
acquisition restarting
R/W 10 ~ 3000
0.01s
bb-46
13146
335Ah
Overcurrent suppression level for
frequency acquisition restart
R/W
(0 to 2.00) * CTL rated
current
0.1A
bb-47
13147
335Bh
Start speed selection for frequency
acquisition restart
R/W 0 ~ 2
1
bb160
13160
3368h
First overcurrent detection level
R/W
(0.20 to 2.20) * ND rated
current
0.1A
bb-61
13161
3369h
Incoming overvoltage selection
R/W 0 ~ 1
1
bb-62
13162
336Ah
Incoming overvoltage level selection
R/W
200V class: 3000 ~ 4100
400V class: 6000 ~ 8200
0.1Vdc
bb-64
13164
336Ch
Ground fault detection selection
R/W 0 ~ 1
1
bb-65
13165
336Dh
Input phase loss selection
R/W 0 ~ 1
1
bb-66
13166
336Eh
Output phase loss selection
R/W 0 ~ 1
1
bb-67
13167
336Fh
Output phase loss detection sensitivity
R/W 1 ~ 100
1%
bb-70
13170
3372h
Thermistor error level
R/W 0 ~ 10000
1Ω
bb-80
13180
337Ch
Over-speed error detection level
R/W 0 ~ 1500
0.1%
bb-81
13181
337Dh
Over-speed error detection time
R/W 0 ~ 50
0.1s
bb-82
13182
337Eh
Operation for speed deviation error
R/W 0 ~ 1
1
bb-83
13183
337Fh
Speed deviation error detection level
R/W 0 ~ 1000
0.1%
bb-84
13184
3380h
Speed deviation error detection time
R/W 0 ~ 50
0.1s
bb-85
13185
3381h
Behavior when the position deviation is
abnormal
R/W 0 ~ 1
1
bb-86
13186
3382h
Abnormal position deviation detection
level
R/W 0 ~ 65535 (*100pls)
1 (*100pls)
bb-87
13187
3383h
Abnormal position deviation time
R/W 0 ~ 50
0.1s
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...