12-14-10
Chapter 12
Inverter Function
12.14.6
Starting after reset
• How to start operation matched with frequency
because the motor is idling at trip reset
• How to start operation with 0 Hz because the brake
is applied after a trip
• Set the start mode after a trip reset or a reset input
via the [RS] terminal (input terminal function 028).
(Ex. 1) Restart operation with 0 Hz: [bb-41]=00
(Ex. 3) Restart with 0 Hz: [bb-41]=00
Parameter
* 1) See "12.14.3 Starting by picking up frequency".
• The restart after reset, which occurs when the
inverter recovers from a reset, is the same as the
mode at power-on.
• If the frequency pull-in restart is used, the rotational
direction of the output frequency is the same as the
command direction at shut-off.
• If a power failure lasts long and the inverter's
internal power supply is lost, recovery will take
place by the restart after reset instead of the restart
after instantaneous power failure/under-voltage.
• In case of the 0 Hz restart, there is no wait time.
(Ex. 2) Frequency pull-in [bb-41]=01 to 03
(Ex. 4) Frequency pull-in [bb-41]=01 to 03
*2) See "12.14.4 Starting with frequency pull-in".
Item
Parameter
Data
Description
Restart after reset
[bb-41]
00
Performs the 0 Hz restart.
01
Performs frequency matching restart.* 1)
02
Performs frequency pull-in restart.* 2)
Retry wait time after
instantaneous power
failure/under-voltage
[bb-26]
0.3~100.0(s)
Sets the wait time after the operation
command.
Q
A
!
Restart with 0 Hz
Operation
command
Motor speed
[RS] Reset
Free-running
Follows [bb-41]
[bb-26]
[RS] Reset
Motor speed
Operation
command
Restart with 0 Hz
Operation
command
Motor speed
[RS] Reset
Free-running
Follows [bb-41]
[bb-26]
[RS] Reset
Motor speed
Operation
command
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...