10-9
Chapter 10
Test Run
(Example: usage 1)
Checking the behavior while the alarm [AL] is on.
• The operation was started.
• P-N voltage monitor optional selection [PA-24] was
set to 01, and P-N voltage monitor optional setting
value [PA-25] was set to the maximum value.
• An overvoltage error [E007] occurred and [AL] was
ON.
Parameter
(Example: usage 2)
Checking the signal output of overload prewarning
level [OL].
• The overload prewarning level [CE106] was set,
and the operation was started.
• Output current monitor optional output selection
[PA-22] was set to 02, and [Ai1] was increased and
decreased.
• [OL] was turned ON because the output current
exceeded the overload prewarning level [CE106].
Item
Parameter
Data
Description
Simulation mode
[PA-20]
00
Disable
01
Enable
Selection of error code for alarm test
[PA-21]
000
~
255
Issues a set error. Errors
not listed in the selection
do not occur.
Output current monitor optional output selection
P-N voltage monitor optional output selection
Output voltage monitor optional output selection
Output torque monitor optional output selection
Frequency adjustment frequency optional output
selection
[PA-22]
[PA-24]
[PA-26]
[PA-28]
[PA-30]
00
Disable
01
Enable (Parameter setting)
02
Enable (Setting by [Ai1])
03
Enable (Setting by [Ai2])
04
Enable (Setting by [Ai3])
05
Enable (Setting by [Ai4])
06
Enable (Setting by [Ai5])
07
Enable (Setting by [Ai6])
Output current monitor optional setting value
[PA-23]
0.0 to 3.0
× Inverter rated current (A)
Treats the set values as
internal output values.
P-N voltage monitor optional setting value
[PA-25]
200V class:
0.0 to 450.0 (Vdc)
400V class:
0.0 to 900.0 (Vdc)
Treats the set values as
internal output values.
Output voltage monitor optional setting value
[PA-27]
200V class: 0.0-300.0(V)
400V class: 0.0-600.0(V)
Treats the set values as
internal output values.
Output torque monitor optional setting value
[PA-29]
-500.0~500.0 (%)
Treats the set values as
internal output values.
Frequency matching frequency optional setting
value
[PA-31]
0.00~590.00 (Hz)
Treats the set values as
internal output values.
Overload prewarning level
[CE106]
Output Current
[OL] output
Output
frequency
[Ai1] was input.
OV Level
P-N Voltage
[AL] Output
Output
frequency
[PA-25] setting
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...