12-13-18
Chapter 12
Inverter Function
Instantaneous power failure non-stop
Deceleration/Stop ([bA-30] = 01)
• This function allows deceleration and stop of the
motor while maintaining the voltage under the
instantaneous power failure non-stop frequency
constant voltage level [bA-32] after the power
supply was shut down during operation.
• If the power supply was shut down during operation,
deceleration starts at the frequency lowered by
deceleration starting width [bA-36] when the
voltage drops to the instantaneous power failure
non-stop function activating voltage [bA-31] or
lower, and then decelerates for the instantaneous
power failure non-stop deceleration time [bA-34].
• In case of regenerative status caused by
deceleration torque during deceleration and if the
internal power supply voltage reaches the
frequency-constant voltage level [bA-32] or higher,
the motor will be at constant speed until the internal
power supply voltage falls below the
overfrequency-constant voltage level [bA-32].
• If the frequency-constant voltage level [bA-32] <
Function starting voltage [bA-31], it works by taking
[bA-32] at the same level as [bA-31]. (However, the
set values will not be changed)
• If the frequency-constant voltage level [bA-32] is
lower than the input voltage multiplied by
√
2, the
constant speed state will be maintained and
deceleration will not take place if the power
recovers while this function is in operation. (Power
should be shut off and turned on again, or [bA-32]
needs to be reset during operation.) The [bA-32]
must be set to a value greater than the input
voltage multiplied by
√
2.
• This function will not be disabled until the operation
stop will be completed. To recover power and
restart the operation while this function is in
operation, input the stop command (operation
command OFF) and then input the operation
command again after the motor stopped.
• If the instantaneous power failure non-stop
deceleration starting range [bA-34] is too large,
sudden deceleration will cause overcurrent tripping.
• If the value of [bA-36] is too low or the
instantaneous power failure non-stop deceleration
time [bA-34] is too long, insufficient regenerative
force will cause undervoltage tripping.
A
!
Time
(sec)
Time
(sec)
[bA-32]
[bA-31]
[bA-34]
[bA-36]
Undervoltage Level
Output
Frequency
(Hz)
Main Circuit DC PS Voltage (V)
Time
(sec)
[IPS] Signal
ON
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...