Summary of Contents for HD67591-232-A1

Page 1: ......

Page 2: ...ation Two Ethernet IP ports Temperature range 40 C 85 C 40 F 185 F For others Ethernet IP products see also the following link Converter Ethernet IP to www adfweb com Product HD67077 M Bus www adfweb com Product HD67595 CAN www adfweb com Product HD67597 DeviceNet Master www adfweb com Product HD67598 DeviceNet Slave www adfweb com Product HD67599 J1939 www adfweb com Product HD67589 NMEA 2000 www...

Page 3: ...ntion and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this document With this Document Code go to web page www adfweb com download and search for the corresponding code on the page Click on the proper Document C...

Page 4: ...es mechanical interlocks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation of this equipment and who have appropriate qualifications for their job RESIDUAL RISKS The device is state of the art and is safe The instrument ...

Page 5: ...onic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual Ethernet IP Modbus Master Converter Document code MN67591_ENG Revision 1 001 Pagina 4 di 22 EXAMPLE OF CONNECTION ...

Page 6: ...m Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual Ethernet IP Modbus Master Converter Document code MN67591_ENG Revision 1 001 Pagina 5 di 22 CONNECTION SCHEME Figure 1a Connection scheme for HD67591 232 A1 ...

Page 7: ...ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual Ethernet IP Modbus Master Converter Document code MN67591_ENG Revision 1 001 Pagina 6 di 22 Figure 1b Connection scheme for HD67591 485 A1 ...

Page 8: ...es in reading and 500 bytes in writing Two directional information between Modbus bus and Ethernet IP bus Mountable on 35mm Rail DIN Power Supply 8 24V AC or 12 35V DC Temperature range 40 C to 85 C CONFIGURATION You need Compositor SW67591 software on your PC in order to perform the following Define the parameter of Ethernet IP line Define the parameter of Modbus line Define the data to Read in M...

Page 9: ...nverter Document code MN67591_ENG Revision 1 001 Pagina 8 di 22 POWER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 8V 24V 12V 35V Consumption at 24V DC Device Consumption W VA HD67591 232 A1 3 5 HD67591 485 A1 3 5 HD67591 xxx A1 Caution Not reverse the polarity power ...

Page 10: ...n of the Dip2 of Dip Switch B The first with Dip2 of Dip Switch B at OFF position is used for the normal working of the device The second with Dip2 of Dip Switch B at ON position is used for upload the Project and or Firmware For the operations to follow for the updating see UPDATE DEVICE section According to the functioning mode the LEDs will have specifics functions see LEDS section Warning Dip1...

Page 11: ... table below LED Normal Mode Boot Mode 1 Device State green Blinks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Serial comm green Change state when receive a Modbus reply Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 Ethernet1 Link green ON Ethernet cable connected OFF Ethernet cable disconnected ON Ethernet cable connected OFF Ethern...

Page 12: ...The Ethernet IP connection must be made using Connector3 and or Connector4 of HD67591 A1 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recomm...

Page 13: ...0Ω resistor it is necessary to put ON dip 1 like in figure The maximum length of the cable should be 1200m 4000 feet Here some codes of cables Belden p n 8132 2x 28AWG stranded twisted pairs conductor foil shield braid shield Belden p n 82842 2x 24AWG stranded twisted pairs conductor foil shield braid shield Tasker p n C521 1x 24AWG twisted pair conductor foil shield braid shield Tasker p n C522 2...

Page 14: ...e software works with MSWindows MS 2000 XP Vista Seven 8 32 64bit When launching the SW67591 the right window appears Fig 2 NEW PROJECT OPEN PROJECT The New Project button creates the folder which contains the entire device configuration A device configuration can also be imported or exported To clone the configurations of a Programmable Ethernet IP Modbus Master Converter in order to configure an...

Page 15: ...n the fields Default Gateway insert the default gateway that you want to use This feature can be enabled of disabled pressing the Check Box field In the field Port insert the number of port In the field Number Byte Input the number of byte from the Ethernet IP to the Converter is defined at maximum it is possible to use 50 byte In the field Number Byte Output the number of byte from the Converter ...

Page 16: ...he field Type insert the data type of the register you would like to read You can choose between the following o Coil Status o Input Status o Holding Register o Input Register In the field Address the start address of the register to be read is defined In the field NPoint insert the number of consecutive registers to be read In the field Poll Time insert the time to make this request In the field ...

Page 17: ...the field NPoint insert the number of consecutive registers to be written In the field Poll Time insert the time to make this request If the field On Change is checked the gateway send the Write request in Modbus when the data change the value In the field Max Error is the number of errors continues that the gateway waits before suspending the poll until the next reboot If is set to zero this func...

Page 18: ...n t know the actual IP address of the device you have to use this procedure Turn off the Device Put Dip2 of Dip Switch B at ON position Turn on the device Connect the Ethernet cable Insert the IP 192 168 2 205 Press the Ping button must appear Device Found Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operatio...

Page 19: ...update Note When you install a new version of the software it is better if the first time you do the update of the Firmware in the HD67591 232 A1 or HD67591 485 A1device Note When you receive the device for the first time you have to update also the Firmware in the HD67591 232 A1 or HD67591 485 A1 device Warning If the Fig 7 appears when you try to do the Update before require assistance try these...

Page 20: ...eno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual Ethernet IP Modbus Master Converter Document code MN67591_ENG Revision 1 001 Pagina 19 di 22 MECHANICAL DIMENSIONS Figure 10 Mechanical dimensions scheme for HD67591 232 A1 and HD67591 485 A1 ...

Page 21: ...591 232 A 1 Connectors Type 1 Removable 5mm Screw Terminal Enclosure Type A 1M 35mm DIN Rail mounting Serial Line 232 RS232 485 RS485 Device Family HD67591 Ethernet IP Modbus Master Converter Order Code HD670591 232 A1 Converter Ethernet IP Modbus Master Converter RS232 serial Order Code HD670591 485 A1 Converter Ethernet IP Modbus Master Converter RS485 serial ACCESSORIES Order Code AC34001 35mm ...

Page 22: ...ther European countries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recycling of electrical and electronic equipment If the product is disposed correctly you will help prevent potential negative environmental factors and human ...

Page 23: ...upport at www adfweb com Together with the request you need to provide detailed information about the problem 2 Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve months it will be repaired or exchanged and returned within three weeks If the product is no longer und...