11-3
Chapter 11
Frequency command 2
11.2.3
Commanding by the multi-speed
terminal
• Where a multi-speed command hasn’t been
entered, the command complies with [AA101].
• Where zero speed is used, select 07 for [AA101].
Frequency command
• Switch the frequency command by ON/OFF inputs
of the multi-speed terminals [CF1] and [CF2].
Parameter
Parameter
Setting function
Set value
[AA101]
Frequency setting by setting on
the operator keypad
07
[FA-01]*1)
Main speed command
0.00Hz
[Ab110]*1)
0th speed of the 1st multi-step
speed ([CF1]OFF/[CF2]OFF)
0.00Hz
[Ab-11]*2)
1st speed of the multi-step
speed ([CF1]ON/[CF2]OFF)
0.00Hz
[Ab-12] *2)
2nd speed of the multi-step
speed ([CF1]OFF/[CF2]ON)
0.00Hz
[Ab-13] *2)
3rd speed of the multi-step
speed ([CF1]ON/[CF2]ON)
0.00Hz
[CA-06]
Terminal No. 6 is for [CF1].
001
[CA-07]
Terminal No. 7 is for [CF2].
002
*1) If [AA101] is set to 07, a change made to either
[FA-01] or [Ab110] parameter will be automatically
reflected to the other parameter. If [FA-01] cannot
be changed or a change is not reflected, it means
that the command destination hasn’t been the
operator keypad due to terminal functions or
setting of [AA101].
*2) Set the frequency command used at the multi-step
speed command.
Operation command 2
11.2.4
Operating using FW/RV terminal
• Select 00 [FW]/[RV] terminal for [AA111] on the
parameter setting screen.
Operation and stop commands
You can operate or stop by ON/OFF inputs of either
the [FW] terminal or [RV] terminal.
Parameter
Parameter
Setting function
Set value
[AA111]
Operation by [FW]/[RV]
terminal
00
[CA-09]
Terminal No. 9 is for [FW].
001
[CA-08]
Terminal No. 8 is for [RV].
002
▼
▼
Input terminals
5
[2CH]
6
[CF1]
7
[CF2]
8
[RV]
COM
COM
Input terminals
7
[CF2]
8
[RV]
9
[FW]
A
[EXT]
COM
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...