12-11-8
Chapter 12
Inverter Functions
3. Terminal switch mode
• Set values of torque limits 1 to 4 ([bA112] to
[bA115]) in all operation states are enabled by the
combination of torque limit switch terminals 1 and 2
(TRQ1, TRQ2) set to the input terminal.
• When torque limit selection [bA110] = 07
(parameter setting) or torque limit mode selection
[bA111] = 01 ([TRQ] terminal switch) is selected,
torque limit 1 to 4 that can be switched by switching
the torque limit switch 1/2 assigned to the input
terminal will be set as shown in the figure on the
right.
Maintain acceleration/deceleration command of
speed control when torque control is switched
• If torque pulsation occurs at the time of canceling
after torque limit operation, enabling [bA116] torque
LAD stop selection may be effective.
Parameter
Input terminal function [CA-01] to [CA-11]
Output terminal [CC-01] to [CC-07]
(e.g.) When the 061 [TRQ1] torque limit switch 1 is
assigned to the input terminal 7 and the 062
[TRQ2] torque limit switch 2 to the input terminal 8
Item
Parameter
Data
Description
Torque limit
selection
[bA110]
00~11
00 (Disable/01)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Ai4 terminal input)/05 (Ai5 terminal input)/
06 (Ai6 terminal input)/07 (Parameter setting)/
08 (RS 485)/09 (Option 1)/
10 (Option 2)/11 (Option 3)
Torque limit
parameter mode
selection
[bA111]
00
Four Quadrant specific
01
[TRQ] terminal switch
Torque limit 1
Torque limit 2
Torque limit 3
Torque limit 4
[bA112]
[bA113]
[bA114]
[bA115]
0.0~500.00(%)
The torque limit function will operate when
output torque exceeds this set value.
Torque LAD
stop selection
[bA116]
00
Disable
01
Enable: retains frequency information
when the torque limit is switched. (at the
time of deceleration operation)
Item
Terminal
name
Data
Description
Enable/disable torque
limit
[TL]
060
Switches enable/disable of the torque limit function.
Torque limit switch 1
[TRQ1]
061
Is the torque limit command switch terminal 1.
Torque limit switch 2
[TRQ2]
062
Is the torque limit command switch terminal 2.
Item
Terminal
name
Data
Description
Under torque limit
[TRQ]
022
Signal turns ON when the torque limit function is
enabled.
A
OFF
OFF
[bA112]
ON
OFF
[bA113]
OFF
ON
[bA115]
ON
ON
[bA114]
TRQ2
T
RQ1
COM
Input terminal function
7 8
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...