STO monitor [dA-45] and status indication on the upper
right of the operator keypad
Error indication
Status transition
STO monitor [dA-45]
data display
contents
(Status indication on
the upper right of the
operator keypad)
Condition
Description
00:Non
(No indication)
<1>
Operation is permitted on both ST1 and ST2 (contact point is ON) and inverter
output is available.
01:P-1A
P-1A
<2>
When operation is permitted on both ST1 and ST2 (contact point is ON), only
ST2 changes to STO (contact point is OFF). Then, operation is permitted (contact
point is ON) on ST1 again for the entire STO switch allowable time [bd-02].
02:P-2A
P-2A
<3>
When operation is permitted on both ST1 and ST2 (contact point is ON), only
ST1 changes to STO (contact point is OFF). Then, operation is permitted (contact
point is ON) on ST1 again for the entire STO switch allowable time [bd-02].
03:P-1b
P-1b
<5>
(1) The P-1A or P-1b status is kept until the STO switch allowable time [bd-02]
has elapsed.
(2) When operation is permitted on both ST1 and ST2 (contact point is ON), only
ST2 changes to STO (contact point is OFF), and then the operation is
permitted (contact point is ON) again.
04:P-2b
P-2b
<6>
(1) The P-12 or P-2b status is kept until the STO switch allowable time [bd-02]
has elapsed.
(2) When operation is permitted on both ST1 and ST2 (contact point is ON), only
ST1 changes to STO (contact point is OFF), and then the operation is
permitted (contact point is ON) again.
05:P-1C
P-1C
<7>
From the status that both ST1 and ST2 is STO (contact point is ON), operation is
permitted (contact point is ON) only on ST2. Then, ST1 is at STO (contact point is
OFF) again for the entire STO switch allowable time [bd-02].
06:P-2C
P-2C
<8>
From the status that both ST1 and ST2 is STO (contact point is ON), operation is
permitted (contact point is ON) only on ST2. Then, ST1 is at STO (contact point is
OFF) again for the entire STO switch allowable time [bd-02].
07:STO
STO
<4>
Both ST1 and ST2 are at STO (contact point is OFF).
Item
Error
Condition
Description
STO shut-off error
[E090]
<9>
If [bd-01] is set to 02, the error occurs when both ST1 and ST2 are input.
STO internal error
[E091]
<10>
The error occurs when internal failure is found. It cannot be canceled by reset operation.
STP path 1 error
[E092]
<11>
If [bd-04] is set to 02, the error occurs at [P-1b].
STP path 2 error
[E093]
<12>
If [bd-04] is set to 02, the error occurs at [P-2b].
00:Non
03:P-1b
02:P-2A
04:P-2b
[E091]
Not recover
01:P-1A
05:P-1C
06:P-2C
07:STO
[E090]
[E092]
[E093]
<1>
<2>
<3>
<4>
<5>
<6>
<7>
<8>
<5>
<6>
<4>
<1>
<4>
<4>
<9>
<10>
<11>
<12>
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...