7-11
Chapter 7
Wire Connection and Optional Devices
7.5.5
Applicable Breakers
200V class
・
When inverter ND rating setting
- When inverter LD/VLD rating setting
* If export to the U.S. or Canada or compliance with UL/cUL
standards is required, you need to use wires and breakers
specified in the UL/cUL standards. For details, see "1.7
Compliance with UL Standards".
* The models described in the table are examples of selection.
When using the device, choose a model that has appropriate
breaking capacity and sensitive current by taking short circuit
current and relevant laws and regulations into consideration
based on the rated current shown in the table.
* The applicable motor capacity is a selection example when
Hitachi IE3 4-pole motor model 60HZ 200VAC (200V class) is
used.
* For the power line diameter, see the "Power line" column in the
table shown in "7.5.4 Recommended Wire Diameter, Wiring
Tools, and Crimping Terminals".
* The electric durability ensured when the magnetic contactor is
used in AC-1 class is 500,000 times, while emergency stop
during motor operation is 25 times.
* If there is emergency stop during motor drive or commercial
operation is performed, choose the magnetic contactor on the
motor side in AC-3 class against the rated current of motor.
* If the rated capacity of inverter is larger than the motor capacity,
choose instruments based on the inverter model.
P1 model
P1-*******
(P1-****)
Applicable
motor
(kW)
Applicable instrument (input voltage 200-220V)
Without power factor improvement reactor (DCL or ACL) With power factor improvement reactor (DCL or ACL)
Earth-leakage breaker (ELB) Magnetic contactor (MC) Earth-leakage breaker (ELB) Magnetic contactor (MC)
Example of
model
Rated current
AC-1
AC-3
Example of
model
Rated current
AC-1
AC-3
P1-00044-L(P1-004L)
0.4
EB-30E
5
HS8
HS8
EB-30E
5
HS8
HS8
P1-00080-L(P1-007L)
0.75
EB-30E
10
HS8
HS8
EB-30E
5
HS8
HS8
P1-00104-L(P1-015L)
1.5
EB-30E
15
HS8
HS8
EB-30E
10
HS8
HS8
P1-00156-L(P1-022L)
2.2
EB-30E
20
HS8
HS8
EB-30E
15
HS8
HS8
P1-00228-L(P1-037L)
3.7
EB-30E
30
HS8
HS20
EB-30E
20
HS8
HS20
P1-00330-L(P1-055L)
5.5
EB-50E
40
HS20
HS25
EB-30E
30
HS8
HS20
P1-00460-L(P1-075L)
7.5
EB-50E
50
HS35
HS35
EB-50E
40
HS20
HS25
P1-00600-L(P1-110L)
11
EB-100E
75
HS50
H65C
EB-100E
60
HS35
HS50
P1-00800-L(P1-150L)
15
RXK125-S
125
H65C
H80C
EB-100E
100
HS50
H65C
P1-00930-L(P1-185L)
18.5
RXK125-S
125
H80C
H100C
EB-100E
100
HS50
H65C
P1-01240-L(P1-220L)
22
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
P1-01530-L(P1-300L)
30
EXK225
200
H125C
H150C
EXK225
150
H80C
H125C
P1-01850-L(P1-370L)
37
RXK250-S
250
H150C
H200C
EXK225
200
H100C
H125C
P1-02290-L(P1-450L)
45
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
P1-02950-L(P1-550L)
55
EX400
400
H200C
H300C
EX400
300
H150C
H250C
P1 model
P1-*******
(P1-****)
Applicable
motor
(kW)
Applicable instrument (input voltage 200-220V)
Without power factor improvement reactor (DCL or ACL) With power factor improvement reactor (DCL or ACL)
Earth-leakage breaker (ELB) Magnetic contactor (MC) Earth-leakage breaker (ELB)
Magnetic contactor (MC)
Example of
model
Rated current
AC-1
AC-3
Example of
model
Rated
current
AC-1
AC-3
P1-00044-L(P1-004L)
0.75
EB-30E
10
HS8
HS8
EB-30E
5
HS8
HS8
P1-00080-L(P1-007L)
1.5
EB-30E
15
HS8
HS8
EB-30E
10
HS8
HS8
P1-00104-L(P1-015L)
2.2
EB-30E
20
HS8
HS8
EB-30E
15
HS8
HS8
P1-00156-L(P1-022L)
3.7
EB-30E
30
HS8
HS20
EB-30E
20
HS8
HS20
P1-00228-L(P1-037L)
5.5
EB-50E
40
HS20
HS25
EB-30E
30
HS8
HS20
P1-00330-L(P1-055L)
7.5
EB-50E
50
HS35
HS35
EB-50E
40
HS20
HS25
P1-00460-L(P1-075L)
11
EB-100E
75
HS50
H65C
EB-100E
60
HS35
HS50
P1-00600-L(P1-110L)
15
RXK125-S
125
H65C
H80C
EB-100E
100
HS50
H65C
P1-00800-L(P1-150L)
18.5
RXK125-S
125
H80C
H100C
EB-100E
100
HS50
H65C
P1-00930-L(P1-185L)
22
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
P1-01240-L(P1-220L)
30
EXK225
200
H125C
H150C
EXK225
150
H80C
H125C
P1-01530-L(P1-300L)
37
RXK250-S
250
H150C
H200C
EXK225
200
H100C
H125C
P1-01850-L(P1-370L)
45
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
P1-02290-L(P1-450L)
55
EX400
400
H200C
H300C
EX400
300
H150C
H250C
P1-02950-L(P1-550L)
75
EX600B
500
H300C
H400C
EX400
400
H200C
H300C
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...