Appendix 1-28
Appendix 1
List of Parameters
*1) P1-01760-H (P1-750H) to P1-03160-H (P1-1320H) shall
be as follows.
[Ub-03]=02: 0.5~10.0 (kHz)
[Ub-03]=00 or 01: 0.5~8.0 (kHz)
Code
Name
Data range
Initial value
Note
Page
bb101
First carrier frequency
[Ub-03]=02: Normal duty
0.5~16.0 (kHz)
[Ub-03]=01: Low duty
0.5~12.0 (kHz)
[Ub-03]=00: Very low duty
0.5~10.0 (kHz)
*1)
2.0
12-12-1
bb102
First sprinkle carrier pattern
selection
00 (Disabled)/01 (Pattern 1 enabled)/
02 (Pattern 2 enabled)/
03 (Pattern 3 enabled)/
00
12-12-4
bb103
First automatic carrier frequency
reduction selection
00 (Disabled)/01 (Enabled: current)/
02 (Enabled: temperature)
00
12-12-2
bb-10
Auto-reset selection
00 (Disabled)/
01 (Enabled with operation command OFF)/
02 (Enable after the setting time)
00
bb-11
Auto-reset alarm selection
00 (Output)/01 (Not output)
00
bb-12
Auto-reset waiting time
0~600 (s)
2
bb-13
Auto-reset count
0~10
3
bb-20
Instantaneous power failure retry
count
0~16/255
0
12-16-7
bb-21
Undervoltage retry count
0~16/255
0
12-16-7
bb-22
Overcurrent retry count
0~5
0
12-13-13
bb-23
Overvoltage retry count
0~5
0
12-13-15
bb-24
Selection of instantaneous power
failure/undervoltage retry
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)/
04 (Trip after frequency matching
deceleration stop)
01
12-16-7
bb-25
Allowable instantaneous power
failure time
0.3~25.0 (s)
1.0
12-16-7
bb-26
Retry wait time after instantaneous
power failure/undervoltage
0.3~100.0 (s)
0.3
12-16-7
bb-27
Instantaneous power
failure/undervoltage tripping
selection during stop
00 (Disabled)/01 (Enabled at stop)/
02 (Disabled at stop and deceleration stop)
00
12-16-7
bb-28
Overcurrent trip/retry selection
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)/
04 (Trip after frequency matching
deceleration stop)
01
12-13-13
bb-29
Retry wait time after overcurrent
0.3~100.0 (s)
0.3
12-13-13
bb-30
Overvotage tripping
retry selection
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)/
04 (Trip after frequency matching
deceleration stop)
01
12-13-15
bb-31
Overvoltage retry standby time
0.3~100.0 (s)
0.3
12-13-15
bb-40
Restart after free-run stop
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)
00
12-14-12
bb-41
Restart after the reset is released
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)
00
bb-42
Frequency matching lower limit
setting
0.00~590.00 (Hz)
0.00
12-14-3
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...