12-15-2
Chapter 12
Inverter Function
12.15.2
Stopping with DC braking
• How to stop the motor when a large moment of
inertia makes it continue rotating even after
deceleration stop
• To use DC braking for stopping, the following
settings are required:
- Set [AF101] DC braking selection to 01
- Set [AF102] Braking mode selection to 00
- [AF105] DC braking force
- Set [AF106] DC braking time to other than 0.0
• To use DC braking with frequency command, the
following settings are required:
- Set [AF101] DC braking selection to 02
- Set [AF102] Braking mode to 01 or 02.
- Set [AF103] DC braking frequency setting to
other than 0.00
- [AF105] DC braking force
- Set [AF106] DC braking time to other than 0.0
Parameter
• The carrier frequency during DC braking depends
on [bb101], but it is limited to at maximum 5 kHz.
Depending on the set braking force, the carrier
frequency may automatically go down to 2 kHz.
• When the motor is stopped by using [DB] external
DC braking function (input terminal function 030),
a high output frequency or a high-inertia load may
cause an overcurrent error or overvoltage error.
Item
Parameter
Data
Description
DC braking selection
[AF101]
00
Internal DC braking: Disabled
01
Internal DC braking: Enabled
02
Internal DC braking: Enabled (The braking
operates only with the frequency command.)
Braking mode
selection
[AF102]
00
Enables the DC braking.
DC braking frequency
setting
[AF103]
0.00~590.00(Hz)
With internal DC braking enabled, DC braking is
started when the output frequency reaches or
becomes less than the frequency set for
stopping.
DC braking delay time
[AF104]
0.00~5.00(s)
Specifies the delay in starting DC braking while
temporally shutting off the output.
DC braking force
[AF105]
0~100(%)
Adjusts the DC braking force. When "0%" is
specified, no braking operation will be performed.
DC braking time
[AF106]
0.00~60.00(s)
Sets the duration for DC braking. This setting is
valid for the [DB] terminal in edge mode or for the
internal DC braking.
When "0.00 s" is specified,
no braking operation will be performed.
DC braking/
edge or level
selection
[AF107]
00
Edge mode (Examples 1-a to 6-a)
01
Level mode (Examples 1-b to 6-b)
Input terminal function
[CA-01]~[CA-11]
030
DC braking is enabled by using the [DB] terminal.
OFF: DC braking is disabled.
ON: DC braking is enabled.
Q
A
!
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...