12-20-3
Chapter 12
Inverter Function
1220.3
Outputting a signal when an
operation command exists
• I want to detect the information that an operation
command has been input to the inverter and
convey to the system.
• Assign the output terminal function 031 [FR]
start-up contact signal to one of [CC-01] to [CC-07]
that corresponds to the output terminal and output
the signal.
• The start-up contact signal 031 [FR] is output while
the inverter accepts operation commands.
• The start-up contact signal [FR] is output in
accordance with the state how the operation
command is accepted even when the destination of
the operation command is not a contact.
• The timing chart is as follows.
(Example) In the case of a terminal command
Parameter
• When the inverter is operated by using terminal
commands, simultaneous inputs of the
forward-direction command [FW] and the
reverse-direction command [RV] will cause a
command mismatch, which is interpreted as the
stop command. •In this case, the [FR] signal will
not be output.
• The signal becomes ON not only when the motor
is operating at normal rotation but also when a
voltage is output to the motor as a function such as
DC breaking.
• When the operation enable signal 101 [REN] has
been assigned and set to OFF, the signal [FR]
becomes OFF because the inverter cannot be
operated.
Item
Parameter
Data
Description
Output terminal function
selection 11-15
[CC-01]~[CC-05]
031
[FR]: The start-up contact signal is output
to the output terminal assigned.
Relay output terminal
function selection 16A-16C
[CC-06]
Relay output terminal
function selection
AL1-AL0/AL2-AL0
[CC-07]
Q
A
!
Forward-direction
command [FW]
Reverse-direction
command [RV]
Start-up contact signal
[
FR]
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...