12-5-6
Chapter 12
Inverter Functions
12.5.7
Disabling the keys on operator
keypad
• Don’t want to let the operator keypad stop
operation when the operation is made under an
external command.
• Don’t want to let the operation made by a
communication command be stopped but want to
reset it in case of a trip.
• When a terminal command or communication
command is given, the operation cannot be
stopped from the operator keypad by setting
[AA-13]=01.
• Set [AA-13]=02 to disable the Stop key and use
the resetting function in case of a trip.
Parameters
• [AA-13] STOP key selection is enabled when the
operation command [AA111] is set to a value other
than the value of the operator keypad (02).
• Unlike SJ700, the communication function on
SJ-P1 continues communication even during
resetting and therefore no idling time is necessary
for the resetting.
• Set [AA-13] to 00: Disabled if a stop command is
given from the operator keypad of the inverter in
case of emergency.
• Usually, operation under an operation command
from other than the operator keypad can be
stopped by using the Stop/Reset key on the
operator keypad.
• When the operation under an external command is
stopped from the operator keypad, the operation
stops for safety. To restart the operation, turn off
the external command and on it again.
• When 102 [DISP] terminal function is ON, the
operator keypad screen is fixed to home screen.
Item
Parameters
Data
Description
Operation
command
selection
[AA111]
00
Run/Stop from the control circuit terminal block. ([FW],
[RV] terminals)
01
Run/Stop from the control circuit terminal block. ([STA],
[STP] terminals)
02
Start/Stop by RS485 communication command.
STOP key
selection
[AA-13]
00
Function disabled Always recognizes stop/reset key
operation.
01
Function enabled The stop/reset key no longer works.
02
Only inverter trips can be reset by the stop/reset key.
Input terminal
function
selection
[CA-01]~
[CA-11]
102
[DISP] terminal function
Q
A
!
!
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...