12-13-11
Chapter 12
Inverter Function
12.13.7
Restarting upon recovery after
instantaneous power failure
• Main power was momentarily turned off due to
instantaneous power failure.
• I want to make restart setting while maintaining the
control power supply in standby by inputting the
P-N voltage into the control circuit.
• I want to connect a 24-V backup power supply to
be able to restart even if the power supply failed.
• When the power supply shows the voltage falling
short of the undervoltage level, you can select
either tripping ([bb-20] = 00) by recovering the
power supply or retrying restarting ([bb-20]
≠
00).
• If the input power supply to the inverter is input
separately to main power supply (R, S, T) and
control power supply (R0, T0), the instantaneous
power failure is detected based on how much the
power to the main power supply (R, S, T) drops.
• When [bb-27] = 00, you can avoid instantaneous
power failure error before the control power supply
is turned off for saving energy while the inverter
output is being stopped.
• When [bb-27] = 02, you can avoid instantaneous
power failure error caused by power shutdown
during deceleration and stop.
Parameters
(Ex. 1) When [bb-20] = 00, tripping occurs
• The judgement of instantaneous power failure of
the inverter is based on the detection of voltage
drop in the main power supply (R, S, T).
• Depending on the fluctuation rate of the main
power supply (R, S, T), errors other than
instantaneous power failure may occur.
• If the input power supply to the inverter is input to
the control power supply (R0, T0) via main power
supply (R, S, T), undervoltage tripping or
undervoltage retry may be triggered first depending
on the operating situation.
• When the power supplied to the control power
supply (R0, T0) is shut off, the power will be lost as
quick as in about 80 ms. In this case, it will be a
power shutdown.
*) The motor will trip after instantaneous power failure
allowable time.
Item
Parameter
Data
Description
Instantaneous power
failure tripping selection
[bb-20]
0~16/
∞
(255)
(Counts)
Sets the retry counts in case of instantaneous power failure.
If this is set to 0, the motor will trip upon recovery from instantaneous
power failure.
Instantaneous power
failure/undervoltage retry
selection
[bb-24]
00
Restarts at 0 Hz
01
Restarts with the frequency matching
02
Restarts upon frequency pull-in
03
Detection speed (frequency) <v2.00 or higher>
04
Trips after decelerating and stopping with the frequency matching
Instantaneous power
failure allowable time
[bb-25]
0.3~25.0(s)
Restarts if the instantaneous power failure time is within the set value.
Instantaneous power
failure/undervoltage retry
standby time
[bb-26]
0.3~100.0(s)
Starts after waiting for the set time upon power voltage recovery.
Instantaneous power
failure/undervoltage
tripping selection during
stop
[bb-27]
00
Disabled
01
Enabled
02
Disabled during stop and deceleration stop
Q
A
!
Control Power Supply
Inverter
Output
Motor Speed
[AL]
Free Running
IP error occurs
(Ex. 2) When [bb-20]
≠
00 and [bb-24] = 00, it
restarts at 0 Hz.
Control Power Supply
Inverter
Output
Motor Speed
[AL]
Free Running
Instantaneous power
failure allowable time
Retry Standby
Time
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...