12.10.4
PID Sleep
PID sleep function
• In the case of using this function, set 01 (output
low) or 02 (SLEP terminal) to PID sleep condition
selection [AH-85].
• You can change the start/cancel time and level of
the sleep operation depending on the usage.
Parameter
Input terminal function
• You can choose cancellation of the PID sleep
status from 01 (deviation amount), 02 (feedback
low), and 03 (WAKE terminal) of the PID wake
condition selection [AH-93].
• In the case of canceling the PID sleep status by
deviation, cancellation will only be activated when
deviation increases in a direction of lower output,
even if PID1 deviation [AH-02] was set to 01 and
PID deviation ± was switched.
Item
Parameter
Data
Description
PID sleep condition selection
[AH-85]
00
Disable
01
Starts sleep operation when output is low
02
Starts operation at the rising edge of
the [
SLEP] terminal
PID sleep start level
[AH-86]
0.00~590.00(Hz)
Is a level of making a judgment of sleep
operation for the output speed when
[AH-85] = 01.
PID sleep operation time
[AH-87]
0.00~100.00(s)
Is stand-by time before shifting to sleep
operation.
Boost selection prior to PID
sleep
[AH-88]
00
Disable
01
Boosts target value before sleep operation.
Boost time prior to PID sleep
[AH-89]
0.00~100.00(s)
Is actuation time prior to PID sleep.
Boost amount prior to PID
sleep
[AH-90]
0.00~100.00(%)
Sets a boost amount to be added to target
value before sleep.
Minimum operation time prior
to PID sleep
[AH-91]
0.00~100.00(s)
Does not start sleep operation until [AH-91]
has elapsed from start.
PID sleep status minimum
retaining
time
[AH-92]
0.00~100.00(s)
Retains the sleep status until [AH-92] has
elapsed, once the sleep operation started.
PID wake condition selection
[AH-93]
01
Cancels the sleep operation when a
deviation amount increases in a
deceleration direction.
02
Cancels the sleep operation when
feedback value decreases.
03
Cancels the operation at the rising
edge of the [
WAKE] terminal
PID wake start level
[AH-94]
0.00~100.00(%)
Cancels the operation when feedback
value goes below the set value when
[AH-93] is 02.
PID wake operation time
[AH-95]
0.00~100.00(s)
Is stand-by time for operation cancellation
when [AH-93] is 02.
PID wake start deviation
amount
[AH-96]
0.00~100.00(%)
Cancels the operation when a deviation
between target value and feedback value
increases when [AH-93] is 01.
Item
Terminal
name
Data
Description
PID sleep start terminal
[SLEP]
057
Starts the sleep function with the terminal
when
[AH-85] = 02.
PID sleep cancel terminal
[WAKE]
058
Cancels the sleep function with the terminal
when [AH-93] = 03.
A
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...