18-8
Chapter 18
Tips/FAQ/Troubleshooting
E005 Motor overload error
The built-in electronic thermal function monitors the
output current of the inverter and when a motor
overload is detected, the inverter turns OFF its
output. The inverter trips according to the setting of
the motor electronic thermal function.
When a motor overload error occurred, the inverter
does not accept a reset input for 10 seconds.
E005
Error occurred
during
acceleration.
• Setting longer acceleration time in [FA-10] can ease the insufficient
acceleration torque.
• When acceleration torque is required, the situation may be
improved by adjusting the boost function in [Hb141], or by
operating the inverter and making adjustments with control method
in [AA121].
• Re-examination of load condition may improve the situation.
• Insufficient acceleration
torque
• Load inertia is large.
• Friction torque is large.
• A function to suppress
overcurrent is at work.
• A factor for overcurrent may have been occurred. Re-examination of
acceleration time or load condition is required.
Error occurred
after long hours of
use.
• The situation may be improved by reducing the motor load, or
performing a system maintenance (e.g., cleaning the fan to be
driven and removing clogging in the duct).
• System environment
changes
• Aging deterioration
• If the issue is not solved by reduction of the load and system
maintenance, aging deterioration of a life-limited component may be
the cause. A repair is required.
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Error occurred
after a fixed period
of operation.
• Operation under heavy
load condition has
continued.
• Re-examination of operation condition or correction of load condition
may improve the situation.
• Thermal level is set high. • When the motor thermal level setting in [bC110] is not appropriate,
re-examination of the setting may improve the situation.
Error occurred
during
deceleration.
• Setting longer deceleration time in [FA-12] can ease the insufficient
regenerative torque.
• When regenerative torque is required, the situation may be
improved by adjusting the boost function in [Hb141], or by
operating the inverter and adjusting with control method in [AA121].
• Re-examination of load condition may improve the situation.
• Load inertia is large.
• A function to suppress
overvoltage is at work.
• Current may increase as a result of suppressing overvoltage.
Re-examination of deceleration time or load condition in [FA-12] is
required.
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...