14-22
Chapter 14
RS485 Communication
14.5.2
EzCOM Settings
• Set a station number for [CF-02] to each inverter of
the EzCOM network, avoiding overlapping a station
number. While doing so, make sure to assign a
station number 01. The inverter with the station
number 01 will be the “controlling inverter”.
• Set the communication selection of controlling
inverter to EzCOM communication’s “controlling
inverter” [CF-09]=02. Set the communication
selection
of
other
inverters
to
EzCOM
communication [CF-09]=01.
Set-up destinations
ALL: Set to all inverters used for EzCOM.
A:
Set to only an inverter for controlling (station
number 01).
B:
Set to inverters other than an inverter for
controlling (station number 01).
• Set the EzCOM communication start method
[CF-22] to the controlling inverter. If you selected
the input terminal start [CF-22]=00, assign 098
[485:EzCOM start] to any of input terminals 1 - 9, A
or B.
• To a master inverter, set the number of transmitting
data,
the
station
number
of
transmission
destination, register of transmission destination,
and register of transmission source that are
required for the master inverter to write the data
(see the following table).
*1) When you provide multiple master inverters, set
consecutive station numbers (01, 02, 03, ...) to
them. If the numbers are not consecutive, the
inverters cannot perform communication.
*2) Note that the relationship between the master
start/end station number settings must be
[CF-
20] ≤ [CF-21].
Item
Parameter
Data
Set-up
Destination
Description
Communication station number
selection *1)
[CF-02]
1~247
ALL
Station number setting
Communication error operation
selection
[CF-06]
00
ALL
Trip
01
ALL
Trips after decelerating and stopping
02
ALL
Ignore
03
ALL
Free-run
04
ALL
Deceleration stop
Communication timeout time
[CF-07]
0.00
ALL
Communication timeout disabled
0.01~100.00
ALL
Unit [s]
Communication waiting time
[CF-08]
0.~1000.
ALL
Unit [ms]
Communication selection
[CF-09]
00
-
Modbus-RTU communication
01
B
EzCOM communication
02
A
EzCOM communication <controlling
inverter>
EzCOM master start station
number *2)
[CF-20]
01~08
A
Setting required for controlling inverter only.
EzCOM master end station
number *2)
[CF-21]
01~08
A
Setting required for controlling inverter only.
EzCOM start selection
[CF-22]
00
A
Start-up by input terminal
01
A
Always communication
Input terminal 1 to 9, A or B
selection
[CA-01]~[CA-11]
098
A
[ECOM]: Starting up of EzCOM
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...