11-5
Chapter 11
Adjustment of I/O terminals - Example 1
11.2.7
Adjusting analog inputs (Ai1/Ai2)
(Example) Adjusting the operation (example for Ai1)
• You can limit the operation range of command
frequency by setting the ratio to the input.
(where a frequency is given via terminal input)
Parameter
Parameter
Setting function
Ai1
Ai2
[Cb-03]
[Cb-13]
Sets a frequency command ratio to a start ratio
for analog input.
[Cb-04]
[Cb-14]
Sets a frequency command ratio to an end ratio
for analog input.
[Cb-05]
[Cb-15]
Sets a start ratio for analog input for 0 to 10 V/0
to 20 mA.
[Cb-06]
[Cb-16]
Sets the end ratio for analog input for 0 to 10 V/0
to 20 mA.
• Ai2 can be adjusted by substituting Ai1 parameter
of the example with Ai2 parameter.
(Example) Making fine adjustment (example for Ai1)
Parameter
Parameter
Setting function
Ai1
Ai2
[Cb-30]
[Cb-32]
Adjusts the zero point of reference line to voltage
input 10 V / current input 20 mA and the
maximum frequency.
[Cb-31]
[Cb-33]
Adjusts the inclination of reference line of
voltage input 10 V / current input 20 mA.
*) Voltage and current inputs can be switched using
the switch on the board.
Adjustment of I/O terminals - Example 2
11.2.8
Adjusting analog outputs
(Ao1/Ao2/FM)
(Example) Adjusting the operation (example for Ao1)
• Firstly, set a value equivalent to 0% output.
• Secondly, adjust a value equivalent to 100%
output.
Parameter
Parameter
Setting function
Ao1
Ao2
FM
[Cd-23]
[Cd-33]
-
Adjusts the zero point of reference
line to voltage output 10 V / current
output 20 mA and data at 100%.
[Cd-24]
[Cd-34]
-
Adjusts the inclination of voltage
output 10 V / current output 20 mA
and data at 100%.
-
-
[Cd-13]
Adjusts the zero point of reference
line to output 100% duty ratio and
data at 100%.
-
-
[Cd-14]
Adjusts the inclination of output
100% duty ratio and data at 100%.
Maximum
frequency
100%
[Cb-04]
[Cb-03]
0
[Cb-05]
[Cb-06]
100
(0V/0mA)
(10V/20mA)
Analog input
(V/mA)
Where [Cb-07]=00,
the command
frequency from 0% to
[Cb-05] is [Cb-03].
100(%)
0
Parallel movement
[Cb-30]=-50.0 (%)
[Cb-30]=0.0 (%)
Maximum
0
50
-50
Change in
[Cb-30]=50.0 (%)
[Cb-31]=200.0 (%)
[Cb-31]=50.0 (%)
[Cb-31]=100.0 (%)
Output scale
t/T (%)
100
0
Parallel movement
Outputting
will be made
in this range.
[Cd-23]=50.0(%)
[Cd-23]=-50.0 (%)
[Cd-23]=0.0 (%)
Maximum
0
50
-50
Full scale (FS)
t/T (%)
100
0
Outputting will
be made in this
range.
[Cd-24]=200.0 (%)
[Cd-24]=50.0 (%)
[Cd-24]=100.0 (%)
Maximum
0
50
-50
[Cd-24]=-50.0 (%)
Change in
inclination
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...