Appendix 1-61
Appendix 1
List of Parameters
Parameter mode (code P)
Code
Name
Data range
Initial value
Note
Page
PA-01
Forced operation mode selection
00 (Disabled)/01 (Enabled)
00
12-17-13
PA-02
Forced operation frequency setting
0.00~590.00 (Hz)
0.00
PA-03
Forced operation rotation direction
command
00 (Normal rotation)/01 (Reverse rotation)
00
PA-04
Commercial power supply bypass
function selection
00 (Disabled)/01 (Enabled)
00
12-17-15
PA-05
Bypass function delay time
0.0~1000.0 (s)
5.0
Code
Name
Data range
Initial value
Note
Page
PA-20
Simulation mode
selection
00 (Disabled)/01 (Enabled)
00
10-9
PA-21
Selection of error code
for alarm test
000~255
000
PA-22
Output current monitor
optional output selection
00 (Disabled)/01 (Enabled: parameter setting [PA-23])
02 (Enabled: set from [Ai1])/03 (Enabled: set from [Ai2])/
04 (Enabled: set from [Ai3])/05 (Enabled: set from [Ai4])/
06 (Enabled: set from [Ai5])/07 (Enabled: set from [Ai6])
01
PA-23
Output current monitor
optional setting value
0.0 to 3.0 × Inverter rated current (A)
0.0
PA-24
P-N voltage monitor
optional output selection
00 (Disabled)/01 (Enabled: parameter setting [PA-25])
02 (Enabled: set from [Ai1])/03 (Enabled: set from [Ai2])/
04 (Enabled: set from [Ai3])/05 (Enabled: set from [Ai4])/
06 (Enabled: set from [Ai5])/07 (Enabled: set from [Ai6])
01
PA-25
P-N voltage monitor
optional setting value
200V class: 0.0 to 450.0 (Vdc)
400V class: 0.0 to 900.0 (Vdc)
200 V class:
270.0
400V class:
540.0
PA-26
Output voltage monitor
optional output selection
00 (Disabled)/01 (Enabled: parameter setting [PA-27])
02 (Enabled: set from [Ai1])/03 (Enabled: set from [Ai2])/
04 (Enabled: set from [Ai3])/05 (Enabled: set from [Ai4])/
06 (Enabled: set from [Ai5])/07 (Enabled: set from [Ai6])
01
PA-27
Output voltage monitor
optional setting value
200V class: 0.0-300.0 (V)
400V class: 0.0-600.0 (V)
0.0
PA-28
Output torque monitor
optional output selection
00 (Disabled)/01 (Enabled: parameter setting [PA-29])
02 (Enabled: set from [Ai1])/03 (Enabled: set from [Ai2])/
04 (Enabled: set from [Ai3])/05 (Enabled: set from [Ai4])/
06 (Enabled: set from [Ai5])/07 (Enabled: set from [Ai6])
01
PA-29
Output torque monitor
optional setting value
-500.0~+500.0 (%)
0.0
PA-30
Frequency adjustment
optional output selection
00 (Disabled)/01 (Enabled: parameter setting [PA-31])
02 (Enabled: set from [Ai1])/03 (Enabled: set from [Ai2])/
04 (Enabled: set from [Ai3])/05 (Enabled: set from [Ai4])/
06 (Enabled: set from [Ai5])/07 (Enabled: set from [Ai6])
01
PA-31
Frequency matching
optional setting value
0.0~590.00 (Hz)
0.00
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...