About the inverter function
12.24.6
Checking the number of input
pulses
• I want to use the pulse string input to count the
pulses for outputting.
• For the pulse counting function, the terminal input
monitoring mode and the phase coefficient
monitoring mode are available.
• When the "Selection of targets for pulse string input
detection [CA-90]" ranges from 00 to 02, the
terminal input monitoring mode becomes valid.
When [CA-90] is set to "03 (pulse count)," the
phase coefficient monitoring mode becomes valid.
• You can monitor the acquired pulses with the pulse
counter monitor served as an accumulation
counter.
• By turning on [PCC] (Clearing of pulse counter),
you can clear the accumulated counter value.
Parameters
• The maximum input pulse in the phase coefficient
monitoring mode becomes a maximum of 32 kpps.
(When the duty ratio is approximately 50%)
• An accumulation counter value cannot be stored.
After the power supply is turned on, the value
becomes zero.
• The maximum input pulse in the terminal input
monitoring mode depends on the settings of the
input terminal response functions [CA-41] to
[CA-51].
Item
Parameter
Data
Description
Input terminal function
[CA-01]~[CA-11]
103
[PLA]: Accepts a pulse input.
104
[PLB]: Accepts a pulse input.
097
[PCC]: Clears the integrated value.
Output terminal function
[CC-01]~[CC-07]
091
[PCMP]: Outputs pulse
compare-match signals.
Selection of targets for
pulse string input
detection
[CA-90]
00
PCNT function
01
Instruction
02
Speed feedback
03
Pulse count
Pulse count
compare-match output
ON level
[CA-97]
0~65535
When the number of pulses reaches
this set value, Turn on [PCMP].
Pulse count
compare-match output
OFF level
[CA-98]
0~65535
When the number of pulses reaches
this set value, Turn off [PCMP].
Maximum value for pulse
count compare-match
output
[CA-99]
0~65535
A one-shot pulse can be achieved
when the value is 0.
When the number of pulses reaches
the set value, the internal counter is
cleared.
Pulse counter monitor
[dA-28]
0~2147483647
Displays the counter integrated value.
Q
A
!
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...