background image

UC300 Universal Converter 

Revision V1.00

Description

The Paradox Universal Converter, the UC300, is an innovative device that allows the CMS to receive events and alarms 
from any security control panel via a Paradox IP receiver. The UC300 provides the link between CID control panel 
security systems and Paradox communication devices, IP150 and PCS250/PCS250G.
UC300 converts Contact ID (CID) events generated by a security panel into Paradox proprietary protocol. Events are 
then forwarded to the monitoring station by the IP150 and/or PCS250/PCS250G.
The UC300 enables end-users to self-monitor their secured location by allowing receipt of instant, SSL-encrypted 
emails via the IP150 and SMS alerts via the PCS250/PCS250G from any location once the system detects activity. 

 Parallel and Backup Connection Methods

The UC300 supports two reporting sequences. Configuring the Reporting Sequence is done through 
BabyWare =>Reporting => Reporting Sequence, see“Reporting Sequence” below. 
Each reporting sequence should be linked to a specific phone number.

Serial Reporting (Backup) 

– defines the primary method for reporting and the number of failed attempts. 

Once the number of failed attempts is reached the UC300 will switch to the backup reporting channels if 
defined. Each reporting sequence supports up to 3 channels (p 2 backups).

Parallel Reporting

 - all report codes are transmitted simultaneously over all available media channels 

(GPRS and IP).

Before You Start

Before you begin, make sure that you have a web-enabled computer. You will also require the following system 
requirements in order to configure your UC300 Universal Converter. 
System requirements include:

Internet access (required for remote access)

IP150 with firmware version 1.27 or higher— You will need the IP module password (default IP150: 

“paradox”

).

PCS250/PCS250G with firmware version 2.06 or higher — If using PCS250 or PCS250G, you will need a SIM card 
from your local wireless service provider with GPRS access

In-Field with firmware version 3.8 or higher

Paradox BabyWare Software version 2.8 or higher

Router if you are connecting an IP150

PSTN  line

CAT-5 Ethernet cable (maximum70m, 295 ft) not included

Note:

Software can be downloaded from our website (

www.paradox.com/

)

Inputs/Outputs I/Os

 Figure 1 – UC300 LEDs

LED Assignment

Power – Green

Dialer indication – Blue

Reset and Firmware upgrade 

Installation

Note:

The control panel must have a valid ground connection. With the control panel grounded there is no need to 
ground the UC300.

Cables

Cables supplied in the box.

UC300 to IP150 4 wire with two 0.8mm socket ends 

IP150/UC300 to PCS250/PCS250G 4 wire with one 0.8mm socket end and one 2.54mm socket end

Note:

Extra cables must be ordered separately. 

 Figure 2 – Connector Cable IP150 to UC300 

 Figure 3 – Connector Cable IP150/UC300 to PCS250/PCS250G

Option #1: IP150 Communication Device 

1.

Clip the UC300 to the system panel box.

2.

Clip the IP150 to the system panel box near the UC300.

3.

Plug in the UC300 to the IP150 using the IP150 Panel port and the UC300 serial port. See Figure 2 for the 
proper cable.

4.

Connect the Tip and Ring from the UC300 to an outgoing telephone jack.

5.

Connect the customer’s control panel Tip and Ring to the UC300 T1 and R1 terminals.

6.

Connect the 12Vdc power supply to a supervised power supply.

7.

Connect an Ethernet cable from the IP150 to the LAN.
When the power is connected the blue and green LEDs will start to flash fast as the module boots up.

 Figure 4 – Connecting the UC300 with an IP150

Option #2: PCS250/PCS250G Communication Device

1.

Clip the UC300 to the system panel box.

2.

Plug in the PCS250/PCS250G cable between the UC300 serial port and the PCS250/PCS250G serial port. See 
Figure 3 for the proper cable.

3.

Connect the Tip and Ring from the UC300 to an outgoing telephone jack.

4.

Connect the customer’s control panel Tip and Ring to the UC300 T1 and R1 terminals.

5.

Connect the 12Vdc power supply to a supervised power supply.

6.

Use a connector cable IP150/UC300 to PCS250/PCS250G and a 307USB to connect to your laptop. This will 
allow you to configure the setup using BabyWare. See Figure 5 insert.

7.

In BabyWare =>Accounts use Connection Option Serial.

When the power is connected the blue and green LEDs will start to flash fast as the module boots up. 

 Figure 5 – Connecting the UC300 with a PCS250/PCS250G

Option #3: Both IP150 and PCS250/PCS250G Communication Devices 

1.

Clip the UC300 to the system panel box.

2.

Clip the IP150 to the system panel box near the UC300.

3.

Plug in the UC300 to the IP150 using the IP150 Panel port and the UC300 serial port. See Figure 2 for the 
proper cable.

4.

Plug in the IP150 to the PCS250/PCS250G using the IP150 PCS250/PCS250G port and the PCS250/PCS250G 
serial port. See Figure 3 for the proper cable.

5.

Connect the Tip and Ring from the UC300 to an outgoing telephone jack.

6.

Connect the customer’s control panel Tip and Ring to the UC300 T1 and R1 terminals.

7.

Connect the 12Vdc power supply to a supervised power supply.

8.

Connect an Ethernet cable from the IP150 to the LAN.

9.

In BabyWare =>Accounts use Connection Option IP Static and connect through the IP150.
When the power is connected the blue and green LEDs will start to flash fast as the module boots up.

 Figure 6 – Connecting the UC300 with an IP150 and PCS250/PCS250G

Using a CA38A/RJ31 Phone Jack (available from your local supplier)

A CA38A phone jack allows the user to disconnect the panel/UC300 in case of a system malfunction and the system 
holds the land line off the hook. The user will then disconnect the panel/UC300 from the line to enable its use by the 

user. 

 Figure 7 – Using a CA38A Device

1

Tip/ring – go to the end user’s land line (not mandatory)

2

T1/R1 – connection to the end user’s control panel telephone line

3

Serial mini type connector – for FW upgrade, IP150 and PCS250/PCS250G connection

4

DC in – supervised power input

5

Two LED indications (green and blue see LED Assignment section)

6

Reset  switch

UC300-EQ01                          03/2015                Printed in Canada

1

2

3

4

5

6

Description 

Green LED Behavior

<9v

Off

9v – 12v 

Slow (1s on, 1s off ) flashing green

12v – 15v

Steady green

15v – 18v 

Fast (0.5s on, 0.5s off ) flashing green

>18v

Off

Description 

Blue LED Behavior

In report listening 

 Steady blue

When data is recognized 

 Flashing blue

Description Special Feature 

Blue and Green LED Behavior

Reset – after holding down the reset button for 5 seconds

Blue and green flash fast 

Reset – after confirmation 

Blue and Green off until reboot complete

Firmware upgrade or no firmware present

Blue Blinking fast

Note:

If you are programming the UC300 using the 307USB disconnect the PCS250/PCS250G, from the 
UC300 and connect the 307USB to the serial port. You may need to replace the serial cable with 
a cable in Figure 3.

Reviews: