7-29
Chapter 7
Wire Connection and Optional Devices
Input terminals
・
All COM terminals are at the same potential.
・
When connecting a power supply between 1-9, A,
B and COM, switch SW5 to the external power
supply (EX).
・
You can switch between the sink/source logic of
input terminals by using SW6.
(Wiring example)
・
[ ] indicates the factory default setting.
Initial terminal function
[RS] Reset
・
Resets when trip occurs.
[SCHG] Switch of frequency command
・
Switches between the main speed command
[AA111](OFF) and auxiliary speed command
[AA112](ON).
[JG] Jogging
・
When operation command is input with [JG]ON,
operation is performed at the frequency set for
[AG-22].
[FRS] Free-run stop
・
The motor performs free-run when [FRS] is ON.
[2CH] 2-stage acceleration/deceleration
・
When [2CH] is ON, the acceleration/deceleration
time 2[AC124]and [AC126] are enabled.
[EXT] External trip
・
When [EXT] is ON, trip [E012] is issued.
[FW] normal rotation and [RV] reverse rotation
Normal
rotation
FW
Reverse
rotation
RV
Description
OFF
OFF
There is no command.
ON
OFF
Forward rotation command operation
OFF
ON
Reverse rotation command operation
ON
ON
There is no command (logic inconsistency).
[CF1] multistage speed 1 and [CF2] multistage speed
2 commands
Multistage
speed 1
CF1
Multistage
speed 2
CF2
Description
OFF
OFF
The set frequency command is enabled
ON
OFF
[Ab-11] frequency command is enabled
OFF
ON
[Ab-12] frequency command is enabled
ON
ON
[Ab-13] frequency command is enabled
*) By configuring CF3 and 4, you can configure up
to 15th speed.
[USP] Prevention of power restoration restarting
・
When [USP] is ON, upon power-on, trip [E013] is
issued if the operation command is issued.
Terminal
symbol
Terminal
name
Description
Electrical characteristics
In
p
u
t
te
rm
in
a
l
D
ig
it
a
l
in
p
u
t
C
o
n
ta
c
t
9, 8, 7,
6, 5, 4,
3, 2, 1
Input
terminal
You can select terminal functions using
the parameter settings corresponding to
each terminal. You can switch between
the sink logic and source logic by
switching SINK/SRC of SW6.
Voltage between each input/COM
・
ON voltage Min. DC18V
・
OFF voltage Max. DC3V
・
Maximum allowable voltage DC27V
・
Load current 5.6mA (at DC27V)
C
o
n
ta
c
t/
p
u
ls
e
A
Pulse
input-A
When [CA-90] is set to 00, A, and B
terminals can be used as input terminals.
You can select terminal functions using
the parameter settings corresponding to
each terminal.
When [CA-90] is not set to 00, they are
used as terminals for pulse string input.
The maximum input pulse is 32kpps.
Voltage between each input/COM
・
ON voltage Min. DC18V
・
OFF voltage Max. DC3V
・
Maximum allowable voltage DC27V
・
Load current 5.6mA (at DC27V)
・
Maximum 32kpps pulse input
B
Pulse
input-B
C
o
m
m
o
n
COM
Common
for input
terminal
Common
terminals
for
digital
input
terminals (1,2,3,4,5,6,7,8,9,A,B).
There are
three COM terminals.
Input
1
[RS]
2
[SCHG]
3
[JG]
4
[FRS]
5
[2CH]
6
[CF1]
7
[CF2]
8
[RV]
9
[FW]
A
[EXT]
B
[USP]
COM
COM
COM
Control circuit terminal
area
SW6
SW5
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...