18-3
Chapter 18
Tips/FAQ/Troubleshooting
18.3 Checking Error Information
18.3.1
Checking trip information
• The inverter generated an error and tripped. You
want to see the information of the moment the error
occurred.
• Up to 10 trips in the past is displayed as the trip
history.
• The latest trip history is displayed on the trip
monitor 1.
• The following data items are displayed on the
monitor:
1) Error factor for trip
2) Output frequency (Hz) at trip
3) Output current (A) at trip
4) Main circuit DC voltage (V) at trip
5) Operation state at trip
6) Cumulative inverter operating time (h) before trip
7) Cumulative inverter power-on time (h) before trip
Parameter
“Detailed monitor” for checking the history
• You can look through the history
with the arrow keys.
• The information of the moment of error occurrence
may not be fetched properly if the inverter is
forcibly turned OFF by its hardware.
• Values of respective data items may be reset to 0
when an error occurred and the inverter entered
the trip condition.
• For a ground fault or a momentary overcurrent
event, the current may be recorded in a value lower
than the actual value.
• The trip monitor and the trip count monitor can be
cleared by initialization of the trip history.
Display of occurring trip
Item
Parameter
Data
Description
Trip monitor 1 to 10
Detailed monitor
See above data
items.
On the parameter monitor, you can view
data items 1) to 7) in sequence by
UP/DOWN keys.
Trip count monitor
Detailed monitor
0 - 65535 (Counts)
Trip count data is stored in the inverter.
Q
A
!
Back
----
46.49Hz
oFW
TRIP
M1
H07
Occurring trip
Motor overload error
E005 15/12/24
22:10
Output frequency : 0.50Hz
Output current : 49.71A
DC voltage
: 274.1Vdc
Status 1
: Run
NRDY
Menu
Details
46.49Hz
oFW
M1
H06
Trip history
Total count 20 times
1. E007 16/07/15 10:10
2. E001 16/07/15 08:55
3. E001 16/07/15 08:52
4. E009 16/07/12 10:10
5. E012 16/07/10 22:52
STOP
Trip history
Total count 20 times
6. E001 16/05/10 19:22
7. E001 16/04/21 20:59
8. E007 16/03/30 23:55
9. E001 15/12/25 01:34
10. E005 15/12/24 22:10
Trip history details (No.10)
Motor overload error
E005 15/12/24
22:10
Output frequency : 0.50Hz
Output current
: 49.71A
DC voltage : 274.1Vdc
Status 1
: Run
Trip history details (No.10)
Motor overload error
Status 3 : Speed control
Status 4 : Overload limit
Status 5 : ----
RUN time : 20256 hr
ON time : 27248 hr
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...