18-38
Chapter 18
Tips/FAQ/Troubleshooting
Operation command is
limited.
Please check operation
command.
• Operation command of command direction
is limited by the setting of [AA114] operation
direction limit.
• The rotation direction is reversed from the
command direction limited according to the
setting of [AA114] operation direction limit
because the frequency command is turned
negative due to calculation of main speed or
auxiliary speed.
• Check the setting of [AA114]
operation direction limit.
• Check the terminal command FW/RW
and the command direction of
communication command.
• Check whether the calculated
frequency command is negative or
not.
Message
Estimated cause(s)
Exemplar measures to be taken
Resetting.
Inverter is being reset.
Press the XX key.
• [RS] terminal is ON.
• Trip reset was performed. (The screen is
transited automatically at trip reset.)
• The inverter is in the condition that
[RS] terminal is ON. Re-examine the
state of input terminal.
Retrying.
Retrying and restarting.
Press the XX key.
• The inverter is waiting for restart.
(This mode is released after the set wait time
has elapsed.)
• The inverter may not start if the incoming
voltage is low.
• If the wait time for restart is long, the
message will continue to be indicated.
See "12.14 Changing the Start Mode".
• If the incoming voltage is low, check
the input voltage.
Main circuit under
instantaneous power
failure.
Power of main circuit is
turned OFF.
Press the XX key.
• The main circuit power supply (R, S, T) is
turned OFF due to lightning strikes, power
supply environment, or other factors.
• Check the state of input power supply.
• The inverter will recover when the
power supply returns.
Main circuit under
insufficient voltage.
Please check the main
circuit power.
Press the XX key.
• The control circuit power supply (R0, T0) has
been input, whereas the main circuit power
supply (R, S, T) has been cut.
• Check the state of input power supply.
• The inverter will recover when the
power supply of main circuit returns.
POWER OFF
POWER OFF
Press the XX key.
• The power supply to the inverter is turned
OFF.
• Check the state of input power supply.
• The inverter will recover when the
power supply returns.
Control power under
insufficient voltage.
Please check the control
power supply.
Press the XX key.
• The control circuit power supply (R0, T0) is
turned OFF.
• Check the state of input power supply.
• The inverter will recover when the
power supply of control circuit returns.
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...