Install and Wire Telephones
Off-Premises Connections
SI Installation and Upgrades
529
June 2004
The multi-pair protector units and the off-premises cabling must be locally engineered. Connectorized
multi-pair protector units (female 25-pair connector) are recommended.
Analog Line Circuit Protectors
on page 529 shows the recommended protectors.
The protectors can be ordered from the Premises Distribution Systems Equipment and Supplies Catalog.
Return to Task List
Voice Terminal Restrictions for Exposed Environments
Return to Task List
The following voice terminals cannot be installed in an exposed environment:
•
7300-type voice terminals connected to TN762B Hybrid Line circuit packs
•
Multi-button Electronic Telephone (MET) sets connected to TN735 Multi-button Electronic
Telephone (MET) Line circuit packs
•
Analog telephones connected to TN746B Analog Line circuit packs
Return to Task List
Digital Out-of-Building Voice Terminal Protection
Return to Task List
For information about specific protectors, see
Installing the ITW Linx Enhanced Protector
on page 530
Installing the 4C3S-75 Enhanced Protector
on page 530
Installing the Data Link Protector
on page 530
Analog Line Circuit Protectors
Primary
1
1 The 3-type protectors should be used only if they are already part of the existing
protection system. A sneak current protector is always required when a 3-type
primary protector is used.
Primary
(with heat coil)
Sneak Current
Protectors
1
3B1A (carbon)
4B1C (carbon)
220029 Fuse
3B1E-W
(wide gap gas tube)
4B1E-W
(wide gap gas tube)
SCP-1
3C1S
(solid state)
4C1S
(solid state)