Release 9si/10si/Communication Manager 1.x to Communication Manager 2.1
Task list: R9si/10si/Communication Manager 1.x to Communication Manager 2.1
SI Installation and Upgrades
47
June 2004
6
Identify and note all of these links.
7
Execute the following commands to see whether the switch has administration:
— list station
— list trunk-group
— list hunt-group
— list data-module
— list announcements
If any command does not complete successfully, escalate the problem immediately. After the
upgrade you will check the same administration to ensure that the translations are intact.
Return to Task List
Disable Scheduled Maintenance and Alarm
Origination
Return to Task List
To prevent scheduled daily maintenance and alarm generation from interfering with the upgrade:
1
Type
change system-parameters maintenance
and press Return.
2
If scheduled maintenance is in progress, set the
Stop Time
field to 1 minute after the current
time.
or
If scheduled maintenance is not in progress, set the
Start Time
field to a time after the
upgrade will be completed.
For example, if you start the upgrade at 8:00 P.M. and the upgrade takes 90 minutes, set the
Start Time
field to 21:30.
CAUTION:
If you do not disable Alarm Origination, the system can generate alarms, resulting in
unnecessary trouble tickets.
3
Type neither in the
Alarm Origination to OSS Numbers
field and press Enter.
NOTE:
Disabling alarm origination prevents the system from generating alarms, thus preventing
unnecessary trouble tickets.
Return to Task List