Install and Connect MCC1 (Multicarrier) Cabinet
Task List: Connect AC power and ground
342
SI Installation and Upgrades
June 2004
Return to Task List
Connect Shorting Cable to J58890CE-2
Return to Task List
CAUTION:
For a cabinet with a battery charger, read the caution label on the 397C battery charger
before disconnecting batteries.
Some cabinets contain a J58890CE-2 AC Power Distribution Unit without an optional battery charger.
Install the shorting cable only when a battery charger is not installed. If you do not install the shorting
cable or a battery charger, then an alarm appears.
1
Set the circuit breakers on the power distribution unit OFF. See
Figure 94
.
2
At the rear of the cabinet, insert the shorting cable (H600-442-G1) into J11. The cable is keyed so
it can fit only 1 way.
Figure 94: Shorting Cable Installation
Temperature Sensor Cable Adapter Cables
H600-476 Adapter Cable
Usage
Group 1 (G1)
24-cell customer-provided battery
Group 3 (G3) (included with
battery cabinet)
24-cell Avaya battery
Figure notes
1
Shorting Cable (H600-442-G1) (If Battery Charger is Not Installed)
2
J11