Install and Administer Trunks
Add DS1 Tie and OPS Trunks
SI Installation and Upgrades
673
June 2004
!
WARNING:
Shut Down DEFINITY AUDIX System (DS1 Tie
and OPS Trunks)
A yellow caution sticker on the system’s power unit notifies you to shut down the AUDIX before
powering down the system.
!
WARNING:
Neglecting to shut down an AUDIX assembly before powering down the system cabinet
where it resides can damage the AUDIX disk.
1
Log into the AUDIX as craft.
NOTE:
If you have a dadmin login and password, you can use them instead of craft and the craft
password.
2
Type
reset system shutdown
and press Enter.
3
Press Enter again to start the shutdown.
The
SHUTDOWN Completed
message displays when the AUDIX is successfully shutdown. This
takes about 2 minutes.
CAUTION:
If leaving AUDIX System in the carrier, back it out about 2 in. (5 cm) to eliminate the
possibility of damage due to power surges.
Return to Task List
Power Down System (DS1 Tie and OPS
Trunks)
Return to Task List
NOTE:
Power down the PPN only if the existing Tone-Clock is being replaced in a standard
reliability system.
1
At the PPN, set the main circuit breaker to OFF.
2
At each EPN, set the main circuit breaker to OFF.