System 75 Small-Cabinet to R8si (Blowback)
Task List: System 75 Small Cabinet to R8si
SI Installation and Upgrades
317
June 2004
4
Type
display communication-interface links
and press Enter.
Status each of the links.
NOTE:
ISDN-PRI D-channel links no longer appear on this screen. (For release 7 and later,
ISDN-PRI resides on the network packet circuit pack.) For release 7 and later, the only
way to determine if an ISDN-PRI D-Channel is up is to use the status signaling group
command.
5
Type
list signaling-group
and press Enter. For each signal, execute
status signal <number>
.
Validate that all the signal groups that should be operational are in service.
6
Execute the following commands and verify that the information is correct:
list station
list trunk-group
list hunt-group
list data-module
For upgrades from systems later than G1,
list ars analysis
For a system with Expert Agent later than G3V3,
list agent
7
For duplicated systems only, execute
status system 1
Return to Task List
Run acceptance tests [75 small upgrade]
Return to Task List
Run any acceptance tests that are appropriate for this upgrade. The acceptance tests are listed in these 3
checklists:
Test single-carrier cabinet systems
Test multi-carrier cabinet systems
Test telephones and other equipment
For details of the tests, see
Test the System
Test Telephones and Other Equipment
Test single-carrier cabinet systems
1
Check System Status for Each Cabinet
2
Check Circuit Pack Configuration
3
Test Time Division Multiplexing Bus in Processor Port Network
4
Test Tone-Clock Boards