Test the System
LED Indicators
492
SI Installation and Upgrades
June 2004
Test SPE Duplication Memory Shadowing Link (if duplicated)
Return to Task List
1
Type
test shadow-link
and press Enter.
2
Verify the screen displays test results similar to
Figure 186, Example Test Results for SPE
Duplication Memory Shadowing Link,
on page 492.
Figure 186: Example Test Results for SPE Duplication Memory Shadowing Link
Return to Task List
Test Duplicated Switch Processing Element Interchange (if duplicated)
Return to Task List
1
If Multi-Carrier Cabinet (MCC1), type status system
cabinet number <1-44>
and press Enter.
or
If Single-Carrier Cabinet (SCC1), type
status system all-cabinets
and press Enter.
2
Verify the screen displays test results similar to
Figure 187, Example System Status Report for All
Cabinets,
on page 493.
3
Note the
MODE
of
SPE 1A
and
1B
.
4
Type
refresh spe
and press Enter.
Command successfully completed
displays.
5
Type
reset system interchange
and press Enter. This causes the terminal to log off.
6
Log in as craft again.
NOTE:
If you have a dadmin login and password, you can use them instead of craft and the craft
password.
7
Note the
MODE
for
SPE 1A
and
1B
should have changed from that noted in Step 3.
TEST RESULTS
Port Maintenance Name Alt. Name Test No. Result Error Code
SHDW-LNK 318 PASS
Command successfully completed