Chapter 8 Logic Instructions
8-199
8_
Parameter
Name
Timing for changing to TRUE
Timing for changing to FALSE
When the MODBUS TCP data
exchange is restored to normal.
Error
When an error occurs in the instruction
execution.
When
Enable
changes from TRUE to
FALSE.
When the correct parameter value is
filled.
Output Update Timing Chart
Enable
Valid
ET H_E rr or
E TH_Err or ID
Case1
Case2
Case3
E rr or
Err orID
Case 1 When
Enable
changes to TRUE,
Valid
changes to TRUE. When
Enable
changes to FALSE,
Valid
changes to FALSE.
Case 2 When an error occurs while
Enable
is TRUE,
Error
changes to TRUE and
ErrorID
shows
corresponding error code.
Error
changes to FALSE and the value in
ErrorID
changes to 0 when
Enable
changes to FALSE.
Case 3 When
Enable
changes to TRUE,
Valid
changes to TRUE.
ETH
_
Error
changes to TRUE and
ETH
_
ErrorID
shows corresponding error code when the MODBUS TCP data sending fails or
timeout occurs during the instruction execution. When
Enable
changes to FALSE,
ETH
_
Error
changes to FALSE and
ETH
_
ErrorID
shows corresponding error code.
Function
ETH_Link_Status is used for watching if an error occurs in the corresponding MODBUS TCP link or the
slave replies with error codes. The firmware of V1.01 and above supports the function.
Error code
Description
How to deal with
101
The TCP link is disabled.
1. Check if the Ethernet connection is
normal.
2. Re-execute ETH_Link_Manage
instruction to enable the MODBUS
TCP data exchange.
102
TCP link timeout
1. Check if the Ethernet connection is
normal.
2. Check if the settings for the
parameters of ETH_Link_Config
instruction are correct.
Summary of Contents for DVP-15MC Series
Page 19: ...DVP 15MC Series Motion Controller Operation Manual 1 4 _1 MEMO...
Page 23: ...DVP 15MC Series Operation Manual 2 4 _2 MEMO...
Page 31: ...DVP 15MC Series Motion Controller Operation Manual 3 8 _3 MEMO...
Page 75: ...DVP 15MC Series Motion Controller Operation Manual 6 26 _6 MEMO...
Page 87: ...DVP 15MC Series Motion Controller Operation Manual 7 12 _7 MEMO...
Page 432: ...Chapter 8 Logic Instructions 8 345 8_ MEMO...
Page 470: ...DVP 15MC Series Motion Controller Operation Manual 10 34 10 MEMO...
Page 878: ...DVP 15MC Series Motion Controller Operation Manual 11 408 11 1 MEMO...
Page 920: ...DVP 15MC Series Motion Controller Operation Manual A 16 A MEMO...
Page 941: ...D 1 D Explanation of Homing Modes Table of Contents D 1 Explanation of Homing Modes D 2...
Page 966: ...DVP 15MC Series Motion Controller Operation Manual D 26 D MEMO...