14-313
14-313
14.3.5. IO unit monitor
You can monitor the XY device variables of the IO unit.
From the project tree, double-click the target project [Online] -> [Monitor] -> [Signal Monitor] -> [IO unit].
The statuses of the input signals are displayed on the upper table, and the statuses of the output signals are
displayed on the lower table.
The signal values can display signed 16-bit integers or signed 32-bit integers in decimals or hexadecimals.
A continuous range for the display signals can be freely set in [Monitor setting].
This function is available in all versions of CR800-R/CR800-Q series controllers and in CR750-Q/CRnQ-700
controller Ver.R3 or later.
Figure 14-42 IO unit monitor
14.3.5.1. Monitor setting
Click the [Monitor setting] button. The PLC IO unit monitor setting screen is displayed.
Set the starting number of each device and indicate the number of lines to display also indicate the data size
display method when displaying signals.
After setting, click the [OK] button.
Figure 14-43 IO unit setting screen
Summary of Contents for 3F-14C-WINE
Page 84: ...8 84 8 84 Figure 8 21 Parameter transfer procedure 1 2 2 ...
Page 393: ...18 393 18 393 Figure 18 1 Starting the Oscillograph ...
Page 413: ...18 413 18 413 Figure 18 24 Output to Robot program Selection ...
Page 464: ...18 464 18 464 Figure 18 72 Starting the Tool automatic calculation ...
Page 545: ...21 545 21 545 Figure 21 55 Hide display of user mechanism ...
Page 624: ...24 624 24 624 Figure 24 4 Document output example ...