XDPP1100 technical reference manual
Digital power controller
Telemetry sense
Peripheral Field name
Access Address
Bits
Description
IMON measurement will occur,
even if selected by ts_muxmode
and ts_muxctrl2.
0: Disabled
1: Enabled
tsen
atsen_meas_en
RW
7000_4C00h [2]
TSADC ATSEN input measurement
enable. When enabled, the TSADC
will measure the ATSEN input when
selected by ts_muxmode and
tx_muxctrl2. When disabled, no
ATSEN measurement will occur,
even if selected by ts_muxmode
and ts_muxctrl2.
0: Disabled
1: Enabled
tsen
btsen_meas_en
RW
7000_4C00h [3]
TSADC BTSEN input measurement
enable. When enabled, the TSADC
will measure the BTSEN input when
selected by ts_muxmode and
tx_muxctrl2. When disabled, no
BTSEN measurement will occur,
even if selected by ts_muxmode
and ts_muxctrl2.
0: Disabled
1: Enabled
tsen
itsen_meas_en
RW
7000_4C00h [4]
TSADC ITSEN measurement enable.
When enabled, the TSADC will
measure ITSEN when selected by
ts_muxmode and tx_muxctrl2.
When disabled, no ITSEN
measurement will occur, even if
selected by ts_muxmode,
ts_muxctrl1 and ts_muxctrl2.
0: Disabled
1: Enabled
tsen
ts_tsidac_antc_sel
RW
7000_4C00h [6]
ATSEN output current source
enable. This current source should
be enabled when using the ATSEN
input to measure an NTC or PTC
temperature sense element. The
current source may be disabled to
use the ATSEN input as a general-
purpose ADC input.
0: Disabled
1: Enabled
tsen
ts_tsidac_bntc_sel
RW
7000_4C00h [7]
BTSEN output current source
enable. This current source should
be enabled when using the BTSEN
input to measure an NTC or PTC