XDPP1100 technical reference manual
Digital power controller
Fault handler
Peripheral Field name
Access Address
Bits
Description
should be set to a positive current.
This hysteresis parameter applies
to all I
IN
faults and warnings as
shown below.
IIN_OC_FAULT:
Asserted when I
IN
is greater than
IIN_OC_FAULT_LIMIT
Deasserted when I
IN
is less than or
equal to (IIN_OC_FAULT_LIMIT-
fault_iin_fault_hyst)
IIN_OC_WARN:
Asserted when I
IN
is greater than
IIN_OC_WARN_LIMIT
Deasserted when I
IN
is less than or
equal to (IIN_OC_WARN_LIMIT-
fault_iin_fault_hyst)
LSB = 0.25 A, range = -4 to 3.75 A
fault
fault_iout_oc_fault_hyst RW
7000_3C08h
(Loop 0)
7000_4008h
(Loop 1)
[15:10] Output overcurrent (IOUT_OC) fault
(warning) deassertion hysteresis.
Internally, the I
OUT
OC fault is
asserted when I
OUT
exceeds
IOUT_OC_FAULT_LIMIT for
fault_iout_oc_fault_cnt samples
without dropping below
(IOUT_OC_FAULT_LIMIT-
fault_iout_oc_fault_hyst). The
samples above
IOUT_OC_FAULT_LIMIT need not
be consecutive, but a single sample
below (IOUT_OC_FAULT_LIMIT-
fault_iout_oc_fault_hyst) will reset
the count.
For the typical case this parameter
should be set to a positive current.
This hysteresis parameter applies
to all I
OUT
OC faults and warnings as
shown below.
IOUT_OC_FAULT:
Asserted when I
OUT
is greater than
IOUT_OC_FAULT_LIMIT
Deasserted when I
OUT
is less than or
equal to (IOUT_OC_FAULT_LIMIT-
fault_iout_oc_fault_hyst)
IOUT_OC_WARN:
Asserted when I
OUT
is greater than
IOUT_OC_WARN_LIMIT
Deasserted when I
OUT
is less than or
equal to (IOUT_OC_WARN_LIMIT-
fault_iout_oc_fault_hyst)
IOUT_OC_FAST_FAULT: