User Manual
188 of 562
V 1.0
2021-08-25
XDPP1100 technical reference manual
Digital power controller
Digital pulse width modulator
Command name
Access Length Address Bits
Description
pwm4_df
[63:56]: PWM4 rising edge dead time,
pwm4_dr
[71:64]: PWM5 falling edge dead time,
pwm5_df
[79:72]: PWM5 rising edge dead time,
pwm5_dr
[87:80]: PWM6 falling edge dead time,
pwm6_df
[95:88]: PWM6 rising edge dead time,
pwm6_dr
[103:96]: PWM7 falling edge dead time,
pwm7_df
[111:104]: PWM7 rising edge dead
time, pwm7_dr
[119:112]: PWM8 falling edge dead
time, pwm8_df
[127:120]: PWM8 rising edge dead
time, pwm8_dr
[135:128]: PWM9 falling edge dead
time, pwm9_df
[143:136]: PWM9 rising edge dead
time, pwm9_dr
[151:144]: PWM10 falling edge dead
time, pwm10_df
[159:152]: PWM10 rising edge dead
time, pwm10_dr
[167:160]: PWM11 falling edge dead
time, pwm11_df
[175:168]: PWM11 rising edge dead
time, pwm11_dr
[183:176]: PWM12 falling edge dead
time, pwm12_df
[191:184]: PWM12 rising edge dead
time, pwm12_dr
FW_CONFIG_DEADTIME_A
DJUSTMENT_THRESHOLD
RW
Word
E4h
[15:0]
Current threshold amps, above which
we use PWM_DEADTIME_ADJUSTMENT
instead of PWM_DEADTIME. Format is
LINEAR11 with exponent = -2. Set to
0000h to disable.
MFR_IOUT_APC
RW
Word
EAh
[15:0]
Current sense APC. Linear11 format
with suggested exponent -8 or -9
depending on magnitude.
Unit = amps
MFR_MIN_PW
RW
Byte
EBh
[7:0]
PWM ramp minimum PW, LSB = 5 ns,
range = 0 to 1275 ns
Note:
PAGE 0 MFR_MIN_PW associated
with PWM ramp0 and PAGE 1
MFR_MIN_PW associated with PWM