2021-08-25
XDPP1100 technical reference manual
Digital power controller
Fault handler
Peripheral Field name
Access Address
Bits
Description
fault
fault_iout_cc_adj
R
7000_3C80h
(Loop 0)
7000_4080h
(Loop 1)
[14:1]
Status register indicating
magnitude of constant current
mode output voltage adjustment
referenced to the VSEN pin (i.e.,
after the V
OUT
sense resistor
divider).
LSB = 156.25 µV, range = 0.0 to
2.55984375 V
fault
fault_iout_cc_en
RW
7000_3C84h
(Loop 0)
7000_4084h
(Loop 1)
[0]
Constant current mode enable for
IOUT_OC_FAULT. Set by FW based
on IOUT_OC_FAULT_RESPONSE.
0: Disabled
1: Enabled
fault
fault_iout_cc_en_fast
RW
7000_3C84h
(Loop 0)
7000_4084h
(Loop 1)
[1]
Constant current mode enable for
MFR_IOUT_OC_FAST_FAULT. Set
by FW based on
MFR_IOUT_OC_FAST_FAULT_RESP
ONSE.
0: Disabled
1: Enabled
faultcom
fault_shut_mask_com
RW
7000_5400h [31:0]
Shutdown mask for
“
common
”
faults. Individual faults are enabled
for shutdown when their
corresponding bit is high. Enabled
faults disable both loop outputs
and assert the shutdown interrupt.
0: Unused
1: Unused
2: IS1 (ISEN) tracking fault
3: IS2 (BISEN) tracking fault
4: Fbal1 fault
5: IS1 (ISEN) PCL fault
6: IS1 (ISEN) SCP fault
7: Fbal2 fault
8: IS2 (BISEN) PCL fault
9: IS2 (BISEN) SCP fault
10: Unused
11: VREF open fault
12: VSEN open fault
13: Unused
14: VRREF open fault
15: VRSEN open fault
16: Unused
17: BVREF_BVRREF open fault
18: BVSEN_BVRSEN open fault
19 to 31: Unused