User Manual
284 of 562
V 1.0
2021-08-25
XDPP1100 technical reference manual
Digital power controller
Fault handler
Command name
Access Length Address Bits
Description
18: UT_FAULT
19: UT_WARN
20: POWER_LIMIT_MODE
21: ISHARE_FAULT
22: VOUT_MAX_MIN_WARN
23: SYNC_FAULT
24 to 31: Unused
MFR_IOUT_OC_FAST_FAU
LT_RESPONSE
RW
Byte
CAh
[7:0]
Instructs the device on what action to
take in response to a fast output
overcurrent fault.
[7:6]: Response
0: Continue operation maintaining I
OUT
at
IOUT_OC_FAULT_LIMIT without regard
to output voltage
1: Continue operation maintaining I
OUT
at
IOUT_OC_FAULT_LIMIT as long as the
voltage remains above
IOUT_OC_LV_FAULT_LIMIT
2: Not supported
3: Shut down and respond according to
retry bits [5:3]
[5:3]: Retry setting
0: Remain disabled until fault cleared
1 to 6: Attempt to restart [5:3] times with
delay [2:0] between restarts
7: Attempt to restart continuously until
commanded OFF
[2:0]: Delay time
0 to 7: Number of delay time units
between restart attempts, unit defined
by FW_CONFIG_FAULTS command
MFR_IOUT_OC_FAST_FAU
LT_LIMIT
RW
Word
D1h
[15:0]
Sets the value of the output current, in
amps, that causes a fast overcurrent
fault condition. The
“
fast
”
overcurrent
uses an unfiltered version of the output
current while the standard overcurrent
fault uses a filtered version of the output
current. The format is LINEAR11. The
hardware LSB is 1 A, suggesting an
exponent of 0.