7B-19 Air Conditioning System: Manual Type
Evacuation
CAUTION
!
Do not evacuate before recovering
refrigerant in A/C system.
NOTE
Once air conditioning system circuit is
opened (exposed) to atmospheric air, system
must be evacuated by using a vacuum pump.
The A/C system should be attached with a
manifold gauge set, and should be evacuated
for approximately 15 minutes.
1) Connect high charging hose (1) and low charging
hose (2) of manifold gauge set (3) (special tool)
respectively as follows:
High charging hose
→
High pressure charging valve
(4) on discharge hose
Low charging hose
→
Low pressure charging valve
(5) on suction pipe
Special tool
(A): 09990–06020
2) Attach center charging hose (6) of manifold gauge
set to vacuum pump (7).
3) Operate vacuum pump, and then open discharge
side valve (Hi) (8) of manifold gauge set.
If there is no blockage in the system, there will be an
indication on high pressure gauge (9).
When this occurs, open the other side valve (Lo)
(10) of the set.
4) Approximately 10 minutes later, low pressure gauge
(11) should show a vacuum lower than –100 kPa (–
1.0 kgf/cm
2
, –760 mmHg, –14.7 psi) providing no
leakage exists.
NOTE
• If the system does not show a vacuum
below –100 kPa (–1.0 kgf/cm
2
, –760 mmHg,
–14.7 psi), close both valves, stop vacuum
pump and watch movement of low
pressure gauge.
• Increase in the gauge reading suggests
existence of leakage. In this case, repair
the system before continuing its
evacuation.
• If the gauge shows a stable reading
(suggesting no leakage), continue
evacuation.
5) Evacuation should be carried out for a total of at
least 15 minutes.
6) Continue evacuation until low pressure gauge
indicates a vacuum less than –100 kPa (–1.0 kgf/
cm
2
, –760 mmHg, –14.7 psi), and then close both
valves.
7) Stop vacuum pump. Disconnect center charging
hose from pump inlet. Now, the system is ready for
charging refrigerant.
Checking A/C System for Pressure Leaks
After completing the evacuation, close manifold gauge
high pressure valve and low pressure valve and wait 10
minutes. Verify that low pressure gauge reading has not
changed.
CAUTION
!
If the gauge reading moves closer to “0”,
there is a leak somewhere. Inspect the tubing
connections and make necessary
corrections. And then, evacuate system once
again and make sure that there are no leaks.
7
8
9
3, (A)
11
10
1
2
5
4
6
I7RW01721011-01
Summary of Contents for 2006 SX4
Page 2: ......
Page 6: ......
Page 22: ...00 15 Precautions...
Page 38: ...0B 7 Maintenance and Lubrication...
Page 378: ...1K 6 Exhaust System...
Page 848: ...6C 46 Power Assisted Steering System...
Page 954: ...7B 89 Air Conditioning System Automatic Type...
Page 1086: ...8B 121 Air Bag System...
Page 1381: ...Paint Coatings 9L 7 I5RW0C9C0005 01 A Apply sealant 1 Hole...
Page 1382: ...9L 8 Paint Coatings I5RW0C9C0006 01 A Apply sealant covering flange end...
Page 1476: ...Prepared by 1st Ed Feb 2007...