6 Vector Control and Applied Functions
6 - 44
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
The position data storage at power shutoff function enables the inverter to store the data of the Current
Position Monitor (d030) into the EEPROM at power shutoff so that the data can be set in the Current
Position Monitor at the next power-on.
This allows you to use the origin position once established by the origin search function continuously
even after turning on the power supply again.
However, to use this function, observe the following precautions:
• To store the Current Position Monitor data at power shutoff, set the Position Store Selection at Power
Off (P081) to 01 (Store).
• The position data storage at power shutoff function stores the position data into the Position Data at
Power Off (P082) when the power supply is shut off. This data will be set in the Current Position Mon-
itor at the next power-on.
Although you can set data in the Position Data at Power Off (P082), the operation is ineffective
because it will be overwritten at the next power shutoff.
Because the Digital Operator of this inverter has a 4-digit display, you can monitor only the upper 4
digits.
To monitor a value over 4 digits, use the computer tool CX-Drive.
• If the motor rotates when the power supply is shut off, the inverter cannot recognize the rotation
amount, which causes position error.
Take measures to prevent motor rotation at power shutoff, for example, by using the brake.
If the motor rotated after power shutoff, perform origin search operation to establish the origin in
advance.
• Even if the brake is applied at power shutoff, the position error may occur due to backlash. Because
this positional error is accumulated, perform origin search once per several startups to eliminate it.
Parameter
No.
Function name
Data
Default
data
Unit
P075
Position Control Mode
Selection
00:
Limit
00
−
P003
Pulse Train Input RP
Selection
01:
Feedback pulse (Enabled only when
1st control is selected)
00
−
P083
Preset Position Data
Position Limit Setting (Reverse Side) (P073)
to Position Limit Setting (Forward Side)
(P072) (
×
1 multiplication)
0
pulse
C001 to
C007
Multi-function Input S1 to
S7 Selection
91:
PSET (Preset position)
−
−
Position Data Storage at Power Shutoff
Parameter
No.
Function name
Data
Default
data
Unit
P081
Position Store Selection at
Power Off
00:
Not store
00
−
01:
Store
P082
Position Data at Power Off
Position Limit Setting (Reverse Side) (P073)
to Position Limit Setting (Forward Side)
(P072) (
×
1 multiplication)
0
pulse
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...