5 - 3
5 Basic Settings
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-
1 Paramet
er Displ
ay and
Paramet
er Initi
alizat
ion
5
5-
1-1 D
ispla
y Select
ion
5-1
Parameter Display and Parameter
Initialization
• You can select the parameters to be displayed on the Digital Operator.
• To display all parameters, set this parameter to 00 (Complete display).
Displays all inverter parameters.
If a specific function is not selected, its related parameter is not displayed.
For details on the display conditions, refer to the following table.
5-1-1
Display Selection
Parameter No.
Function name
Data
Default data
Unit
b037
Display Selection
00:
Complete display
00
*1
*1. The default data was changed from the previous model.
−
01:
Individual display of functions
02:
User setting
+
d001, F001, b037
03:
Data comparison display
04:
Basic display
05:
Monitor (d***) display only
+
b037
U001 to U032
User Selection 1 to
User Selection 32
no:
No registration
no
−
d001 to P196: Select the parameter number you want
to display.
Complete Display (b037 =00)
Individual Display of Functions (b037 =01)
No.
Display condition
Parameters displayed when condition is met
1
To display parameters
when 2nd control (SET ter-
minal) is selected
C001 to C007 = 08
F202, F203, A201 to A204, A220, A241 to A247, A261,
A262, A281, A282, A292 to A296, b212, b213, b221 to
b223, C241, H202 to H206, H220 to H224, H230 to
H234
2
To display parameters
when 1st Control Method is
set to Sensorless vector
control
A044 = 03
d009, d010, d012, b040 to b046, C054 to C059, H001,
H005, H020 to H024, H030 to H034, P033, P034, P036
to P040
3
To display parameters
when 2nd Control Method
is set to Sensorless vector
control
C001 to C007 = 08 and A244 =
03
d009, d010, d012, b040 to b046, C054 to C059, H001,
H205, H220 to H224, H230 to H234, P033, P034, P036
to P040
4
To display parameters
when 1st/2nd Control
Method is set to Free V/f
setting function
A044 = 02, or C001 to C007 =
08 and A244 = 02
b100 to b113
5
To display parameters
when free-electronic ther-
mal function is enabled
b013 = 02, or C001 to C007 =
08 and b213 = 02
b015 to b020
6
To display parameters
when 1st Control Method is
set to V/f control (constant
torque or reduced torque)
A044 = 00 or 01
A041 to A043, A046, A047
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...