2 Design
2 - 20
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
z
3-phase 400-V class
*1. The wire size is based on H-IV wire (with a heat resistance of 75°C).
*2. For compliance with the UL standard requirements, be sure to perform wiring according to
A-4 UL/cUL Stan-
dards Cautions
on page A-10.
z
Single-phase 200-V Class
*1. The wire size is based on H-IV wire (with a heat resistance of 75°C).
*2. For compliance with the UL standard requirements, be sure to perform wiring according to
A-4 UL/cUL Stan-
dards Cautions
on page A-10.
Model
Heavy/
Light load
mode
Maximum
applicable
motor
capacity
[kW]
Rated
input
current
[A]
Power cable,
ground cable
[mm
2
]
*1*2
Terminal
screw
size
Tightening
torque
[N
·
m]
*2
Molded
case
circuit
breaker
(MCCB)
*2
3G3MX2-A4004-V1
Heavy load
0.4
1.8
AWG16 (1.25)
M4
1.4
5 A
Light load
0.75
2.1
AWG16 (1.25)
5 A
3G3MX2-A4007-V1
Heavy load
0.75
3.6
AWG16 (1.25)
M4
1.4
5 A
Light load
1.5
4.3
AWG16 (1.25)
10 A
3G3MX2-A4015-V1
Heavy load
1.5
5.2
AWG16 (1.25)
M4
1.4
10 A
Light load
2.2
5.9
AWG16 (1.25)
10 A
3G3MX2-A4022-V1
Heavy load
2.2
6.5
AWG14 (2.0)
M4
1.4
10 A
Light load
3.0
8.1
AWG14 (2.0)
15 A
3G3MX2-A4030-V1
Heavy load
3.0
7.7
AWG14 (2.0)
M4
1.4
15 A
Light load
4.0
9.4
AWG14 (2.0)
15 A
3G3MX2-A4040-V1
Heavy load
4.0
11.0
AWG12 (3.5)
M4
1.4
20 A
Light load
5.5
13.3
AWG12 (3.5)
20 A
3G3MX2-A4055-V1
Heavy load
5.5
16.9
AWG12 (3.5)
M5
3.0
30 A
Light load
7.5
20.0
AWG10 (5.5)
30 A
3G3MX2-A4075-V1
Heavy load
7.5
18.8
AWG10 (5.5)
M5
3.0
30 A
Light load
11
24.0
AWG10 (5.5)
50 A
3G3MX2-A4110-V1
Heavy load
11
29.4
AWG10 (5.5)
M6
3.9 to 5.1
50 A
Light load
15
38.0
AWG6 (14)
60 A
3G3MX2-A4150-V1
Heavy load
15
35.9
AWG6 (14)
M6
3.9 to 5.1
60 A
Light load
18.5
44.0
AWG6 (14)
75 A
Model
Heavy/
Light load
mode
Maximum
applicable
motor
capacity
[kW]
Rated
input
current
[A]
Power cable,
ground cable
[mm
2
]
*1*2
Terminal
screw
size
Tightening
torque
[N
·
m]
*2
Molded
case
circuit
breaker
(MCCB)
*2
3G3MX2-AB001-V1
Heavy load
0.1
1.3
AWG16 (1.25)
M3.5
1.0
5 A
Light load
0.2
2.0
AWG16 (1.25)
5 A
3G3MX2-AB002-V1
Heavy load
0.2
3.0
AWG16 (1.25)
M3.5
1.0
5 A
Light load
0.4
3.6
AWG16 (1.25)
5 A
3G3MX2-AB004-V1
Heavy load
0.4
6.3
AWG16 (1.25)
M3.5
1.0
10 A
Light load
0.55
7.3
AWG16 (1.25)
15 A
3G3MX2-AB007-V1
Heavy load
0.75
11.5
AWG12 (3.5)
M4
1.4
15 A
Light load
1.1
13.8
AWG12 (3.5)
20 A
3G3MX2-AB015-V1
Heavy load
1.5
16.8
AWG10 (5.5)
M4
1.4
20 A
Light load
2.2
20.2
AWG10 (5.5)
30 A
3G3MX2-AB022-V1
Heavy load
2.2
22.0
AWG10 (5.5)
M4
1.4
30 A
Light load
3.0
24.0
AWG10 (5.5)
50 A
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...