5 Basic Settings
5 - 48
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
The multi-function input terminals can be set to either NO (NO contact) or NC (NC contact) individually.
This manual describes each function with the Multi-function Input S1 to S7 Operation Selection (C011
to C017) set to 00 (NO: NO contact). Note that the operations of set signals are reversed when you set
them to 01 (NC: NC contact).
*1. NO contact: ON when closed, OFF when open
NC contact: ON when open, OFF when closed
• Set the response time for each multi-function input S1 to S7 terminal independently.
This function is effective for removing noise caused by chattering etc.
• If the terminal input becomes unstable because of chattering, increase the set value.
However, increasing the set value results in a slow response.
The setting range is 0 to 200, which provides a response time of approximately 2 to 400 ms.
*1. When 0 is set, the response time is 2 ms.
• To input the forward and reverse RUN commands via the control circuit terminals, set the Multi-func-
tion Input S1 to S7 Selection (C001 to C007) to 00 (FW) and 01 (RV).
• By default, the Multi-function Input S1 Selection (C001) is set to 00 (FW) and the Multi-function Input
S2 Selection (C002) is set to 01 (RV), respectively.
• To input the RUN command via these control circuit terminals, set the 1st/2nd RUN Command Selec-
tion (A002/A202) to 01 (Control circuit terminal block).
• If the terminals FW and RV turn ON simultaneously, the inverter will stop without displaying any
alarm. It will start operating again when either of these terminals turns OFF.
5-9-2
Multi-function Input Operation Selection
Parameter
No.
Function name
Data
Default
data
Unit
C011
Multi-function Input S1 Operation
Selection
00:
NO (NO contact)
00
−
C012
Multi-function Input S2 Operation
Selection
01:
NC (NC contact)
C013
Multi-function Input S3 Operation
Selection
• Each multi-function input termi-
nal S1 to S7 can be set indepen-
dently to either an NO contact or
NC contact input terminal.
*1
• The terminal allocated to 18 (RS:
Reset) cannot be set to NC
contact. Be sure to set the NO
contact.
C014
Multi-function Input S4 Operation
Selection
C015
Multi-function Input S5 Operation
Selection
C016
Multi-function Input S6 Operation
Selection
C017
Multi-function Input S7 Operation
Selection
Related functions
C001 to C007
5-9-3
Input Terminal Response Time
Parameter
No.
Function name
Data
Default
data
Unit
C160 to
C166
Multi-function Input S1 to S7
Response Time
0. to 200. (
×
2 ms)
*1
1.
ms
5-9-4
Forward RUN Command (FW) and Reverse RUN Command (RV)
Parameter
No.
Function name
Data
Default
data
Unit
C001 to
C007
Multi-function Input S1 to S7
Selection
00:
FW (Forward)
−
−
01:
RV (Reverse)
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...