2 Design
2 - 8
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
To install the terminal block cover, reverse the removal procedure.
Install the terminal block cover on the inverter from the top and press it until you here a click.
Removing the terminal block cover and each connector cover reveals terminal blocks, connectors, and
switches arranged as shown below.
Installing Terminal Block Cover
2-2-2
Terminal Blocks
Name
Description
Terminating resistor selec-
tor switch
The switch for switching ON/OFF the RS-485 terminal on the control circuit terminal
block. When ON, the terminal is connected to the built-in 200-
Ω
terminating resistor.
Safety function selector
switch
Turn this switch ON to use the safety function. Before you turn ON/OFF this switch,
be sure to turn off the power supply. For details, refer to
7-10 Safety Function (Under
Application for Standards)
on page 7-97.
EDM function selector
switch
Turn this switch ON to use the EDM output of the safety function. Before you turn
ON/OFF this switch, be sure to turn off the power supply. For details, refer to
7-10
Safety Function (Under Application for Standards)
on page 7-97.
USB connector
The mini-B type USB connector for connecting a computer.
Use this connector to connect the inverter to the Inverter/Servo support tool
CX-Drive.
Connector for Digital
Operator
The connector for connecting the Digital Operator.
Connector for Option Unit
The connector for connecting an option unit.
Use this connector to connect such as a communications option unit.
Control circuit terminal
block A, B
The terminal block for connecting various digital/analog I/O devices used for inverter
control.
Relay output terminal
block
The SPDT contact terminal block for relay output.
Main circuit terminal block The terminal block for connecting the main power supply for the inverter, outputs to
the motor, Braking Resistor, etc.
Safety function selector switch
Disabled
(Factory default)
Enabled
Terminating resistor
selector switch
OFF
(Factory default)
ON
USB connector (mini-B)
Connector for Digital Operator
(RJ45)
EDM function selector switch
Terminal P1
(Factory default)
EDM output
Control circuit terminal block A
Control circuit terminal block B
Main circuit terminal block
Connector for Option Unit
Relay output terminal block
Charge indicator
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...